How to Read a HEPA Datasheet: MPPS, Test Methods and Why a Leak Beats a Class

By the NextAir Systems engineering team. Last reviewed October 2026.

A HEPA datasheet gives you a percentage that looks definitive. It is a precise number, but it is a precise number about one specific thing, measured one specific way, and it says nothing about what happens once the filter is in the frame. Reading it well means knowing what that thing is.

This guide explains the two measurement conventions on datasheets, shows how to compare them, and then does the arithmetic that most buyers miss: how little bypass it takes to make a very good filter perform like an ordinary one.

The short version

  • EN 1822 grades filters by efficiency at the most penetrating particle size (MPPS), which is where the filter is weakest. H13 is at least 99.95% and H14 at least 99.995%.[1]
  • US-style test types are defined at a fixed 0.3 µm: types A, B and E at 99.97%, type C at 99.99% and type D at 99.999%.[2]
  • A bypass of 0.1% of the airflow limits an H14 installation to an overall efficiency of about 99.9%, and an H13 to nearly the same figure.
  • That is why a datasheet class is not a performance guarantee, and why installed leak testing is part of any serious specification.

Two conventions on the datasheet

The first is the European convention, EN 1822 (and its ISO equivalent). Efficiency is measured at the MPPS, the particle size at which the filter performs worst, which for a fibrous filter is typically around 0.1 to 0.2 µm. Classes run from E10 up to U17, and the two that most people mean by HEPA are H13 (at least 99.95%) and H14 (at least 99.995%).[1] Because it tests the weakest point, an EN 1822 figure is a conservative one.

The second is the US convention, in which filter types are tested at a fixed particle size. In one summary of the IEST recommended practice, types A, B and E are rated at 99.97% at 0.3 µm, type C at 99.99%, and type D at 99.999%. Some types are tested at 0.1 to 0.2 or 0.2 to 0.3 µm instead.[2] The widely quoted 99.97% at 0.3 µm is this convention. It is a different test from EN 1822, so a 99.97% at 0.3 µm and an H13 at 99.95% at MPPS are close but not interchangeable.

What else is on a good datasheet

  • The standard and class, with the test report number. A claim of HEPA-type without a class is not a specification.
  • Whether each filter is individually tested, and by scanning or by probe. Scan testing finds local leaks. A single overall efficiency does not.
  • Initial pressure drop at rated flow, and the final pressure drop for change-out.
  • Frame, gasket and seal type. Whether the filter performs as rated depends on the seal.
  • Rated airflow and dimensions, so you can compute face velocity as in the face area guide.

Leak arithmetic

A filter in a housing has two paths for particles: through the media, where penetration is small, and around it, where it is not. If a fraction b of the airflow bypasses the filter and the media has penetration p, the overall penetration is b + (1 − b) × p. For an H13 the media penetration is at most 0.05% and for an H14 0.005%. The table shows what happens as the bypass grows.

Bypass (share of airflow)Overall efficiency, H13 mediaOverall efficiency, H14 media
none99.9500%99.9950%
0.01%99.9400%99.9850%
0.10%99.8500%99.8950%
1.00%98.9505%98.9950%

Worked example. With no bypass, the H14 beats the H13 by a factor of ten in penetration. With a bypass of 0.1% of the air around the frame, both end up near 99.8500% and 99.8950%, which is the same result for practical purposes, and a long way short of H14’s nominal 99.995%. The extra cost of the higher class has been spent for nothing. A bypass of 1% brings both to 98.9505%, which is only a 99% filter.

The numbers are straightforward arithmetic, and the lesson is practical. Spending on a higher class only pays if the installation is sealed to a standard that matches it.

One practical point on testing. Factory scan testing proves the filter media and the frame bond are sound when the filter leaves the plant. It cannot prove the seal against your housing, which is made on site by whoever fits the filter. The installed test is the only check on that second path, and for the higher classes it is not optional in any project that cares about the number on the datasheet.

What to put in the specification

  1. The filter class under EN 1822 (and ISO 29463 where used), or the IEST type and test particle size, and the test report.
  2. Individual scan or probe testing of each filter before delivery.
  3. A seal type suited to the class, such as a gel or knife-edge seal for high classes, with a gasket that does not take a set.
  4. An installed leak test, with a stated acceptance limit, done in place after fitting. The method and the limit should come from the standard your project follows.
  5. A pressure drop limit, and a plan for changing the filter that does not break the seal of its neighbours.

For the other ratings you will meet on the same datasheet page, our guide to MERV, ISO 16890 and EN 1822 lines the systems up, and the cost of running a bank is in change-out economics.

Where this fits with NextAir

NextAir’s NAP systems offer HEPA stages in 610 × 610 mm modules, with the frame and sealing arrangements specified for the class. Tell our air purification system manufacturer team the class you need and the leak-test regime your project follows, and we will propose the construction. Our centralized air purification guide covers the system, and pharmaceutical describes where HEPA stages are most often required.

Sources

  1. Camfil. Comparison chart: ASHRAE 52.2, ISO 16890, EN 779, EN 1822.
  2. APC Filters. Air Filter Types and Classifications (comparison of ASHRAE 52.2, EN 779, EN 1822 and IEST-RP-CC001).

Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.

Frequently Asked Questions

What is MPPS?

The most penetrating particle size: the size at which a given filter captures least efficiently. EN 1822 grades a filter by its efficiency at that size.

What is the difference between H13 and H14?

H13 has an initial efficiency of at least 99.95% at MPPS and H14 at least 99.995%. An H14 lets through about one-tenth as many particles.

Is H13 the same as HEPA?

It is the European class most often described as HEPA. US HEPA uses a fixed 0.3 µm test with 99.97%, so the two are close but defined differently.

Why does a high-class filter sometimes underperform?

Because air can bypass the media through leaks around the seal and frame. A small bypass can limit overall efficiency to well below the class of the media.

What is an installed leak test?

A test in place after fitting, in which an aerosol challenge is applied upstream and the downstream side is scanned for leaks. The method and acceptance limit come from the standard the project follows.