MERV, ISO 16890 and EN 1822: Reading Air Filter Ratings Without the Marketing

By the NextAir Systems engineering team. Last reviewed October 2026.

Three rating systems sit on the filters in a typical air handling unit, and the datasheets rarely explain how they relate. MERV is the American scale from 1 to 16. ISO 16890 is the global particulate standard that classes a filter by how well it catches PM1, PM2.5 and PM10. EN 1822 covers the high-efficiency filters, E11 through U15, including what most people mean by HEPA.

None of them is difficult once you see what each is measuring. This guide lines them up, shows what the numbers mean as particles that get through rather than particles caught, and ends with the few lines to put in a specification so the supplier cannot hide behind a vague label.

The short version

  • ISO 16890 classes a filter as ISO Coarse, ePM10, ePM2.5 or ePM1, and a filter that does not reach 50% on any fine-particle size is simply coarse.[1][2]
  • As a rough guide, ISO Coarse corresponds to MERV 1 to 8, ePM10 to 9 to 10, ePM2.5 to 11 to 12 and ePM1 to 13 to 16, but the standards do not report the same thing.[1]
  • EN 1822 classes are defined by efficiency at the most penetrating particle size: H13 is at least 99.95% and H14 at least 99.995%.[3]
  • Penetration, not efficiency, shows the gap: an H14 lets through 1/10 as many particles as an H13, and 1/1,000 as many as an E11.

ISO 16890: classify by particle size

ISO 16890 replaced two regional standards that measured similar things in ways that defied comparison: ANSI/ASHRAE 52.2 in the US and EN 779 in Europe.[2] It reports efficiency against three particle size ranges, PM1 (0.3 to 1 µm), PM2.5 (0.3 to 2.5 µm) and PM10 (0.3 to 10 µm), written ePM1, ePM2.5 and ePM10. The class comes from the most demanding range the filter passes at 50% or better, and a filter that cannot reach 50% on any of them is ISO Coarse.[1][2]

The rule has a twist. To qualify as ePM1 or ePM2.5, both the initial efficiency and the discharged, or conditioned, efficiency must exceed 50%.[3] That matters because some media, especially electrostatically charged ones, lose efficiency in service, and the standard exposes it. A filter is then reported with its efficiency, for example ePM1 65%.

ISO 16890 groupQualificationRough MERV equivalent
ISO CoarseISO Coarse (ePM10 below 50%)about MERV 1 to 8
ISO ePM10ePM10 of at least 50%about MERV 9 to 10
ISO ePM2.5ePM2.5 of at least 50%about MERV 11 to 12
ISO ePM1ePM1 of at least 50%about MERV 13 to 16

The equivalents come from NAFA’s guide, which stresses that although the tests are similar, the reported values do not report the same thing, so the table is a guide to expectations and not a conversion.[1] A caution from industry commentary is also worth keeping in mind: some data show negligible real difference between MERV 8 and MERV 11, and a big jump between MERV 11 and MERV 13, so a number in the middle of the scale does not always mean what you would expect.[2]

EN 1822: the high-efficiency end

Above ISO’s ePM1 sit the E, H and U classes of EN 1822. They are tested at the most penetrating particle size, MPPS, which is the size the filter catches least well and is typically around 0.1 to 0.2 µm. The classification by initial efficiency at MPPS is shown below.[3] The last two columns are our arithmetic: penetration is 100 minus efficiency, and the last column compares each class with an E11.

ClassInitial efficiency at MPPSPenetration (best case)Particles passing relative to an E11
E11at least 95%5%1 in 1
E12at least 99.5%0.5%1 in 10
H13at least 99.95%0.05%1 in 100
H14at least 99.995%0.005%1 in 1,000
U15at least 99.9995%0.0005%1 in 10,000

Read the last column as relative leakage. An E12 passes one particle for every ten that an E11 passes, an H13 one for every hundred, an H14 one for every thousand, and a U15 one for every ten thousand. It is why a leak test at installation matters more than a class step, a point we take up in how to read a HEPA datasheet.

What to write in a specification

  • The ISO 16890 class and the efficiency, for example ePM1 65%, not a MERV number alone. If you need MERV, state the ASHRAE 52.2 test.
  • The initial pressure drop at rated airflow, and the final pressure drop at which the filter is changed.
  • For high-efficiency filters, the EN 1822 class and the test report, and whether each filter is individually scanned or probed.
  • The dust holding capacity or expected life, so the energy and change-out cost can be compared. The energy side is in face area, velocity and energy.
  • The frame and gasket details. A filter that is rated well and fitted badly is a bypass.

Choosing a class

Class follows purpose. A coarse prefilter protects the coil and the next filter from large dust. An ePM10 or ePM2.5 filter, the usual workhorse of an HVAC system, removes most of the visible dust and a good share of the fine particles. An ePM1 stage is the practical way to cut fine particles indoors, and is the usual choice where outdoor air is poor. Beyond that, H13 and H14 stages belong where particle counts are regulated: cleanrooms, pharmaceutical suites and some hospital areas. Stacking classes in sequence extends the life of the expensive final stage, which is the logic of the arrangement in our guide to centralized air purification.

How much the outdoor air matters is the subject of the WHO guideline article.

Where this fits with NextAir

NextAir’s centralized air purification systems stage prefilters, fine filters and, where required, HEPA and UV-C modules in 610 × 610 mm cartridges, from NAP-0500 to NAP-20000. Tell our air purification system manufacturer team the particle size you must control and the airflow, and we will propose the filter classes with their pressure drops. See also pharmaceutical applications.

Sources

  1. National Air Filtration Association (NAFA). ISO 16890 user guide: understanding ePM and ISO Coarse.
  2. Combined Cycle Journal. ISO 16890, a new global test standard, facilitates comparison of alternative filters.
  3. Camfil. Comparison chart: ASHRAE 52.2, ISO 16890, EN 779, EN 1822.

Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.

Frequently Asked Questions

What is the difference between MERV and ISO 16890?

MERV is the ASHRAE 52.2 scale from 1 to 16. ISO 16890 reports efficiency separately for PM1, PM2.5 and PM10. They are tested similarly but report different things, so equivalence is approximate.

What does ePM1 65% mean?

That the filter captures at least 65% of particles between 0.3 and 1 µm, averaged between its initial and conditioned state, and that both states exceed 50%.

Is H13 the same as HEPA?

H13 is an EN 1822 class with at least 99.95% efficiency at the most penetrating particle size. The US HEPA definition uses 99.97% at 0.3 µm, so the two are close but not identical.

Is a higher MERV always better?

Not always. Efficiency rises with MERV, but so can pressure drop, and the gain between some adjacent classes is small. Match the class to the particle size you need to control.

What should I ask a filter supplier for?

The ISO 16890 class with efficiency, the initial and final pressure drop, the test report, the dust holding capacity and the frame and gasket construction.

Talk to Our Engineering Team

Call +91-9311805618 or use our contact form for a facility-specific recommendation.

Contact Us