How Much Water Does a Desiccant Dehumidifier Remove? What Published Datasheets Show

By the NextAir Systems engineering team. Last reviewed October 2026.

When we checked our own ND-series ratings against the market, the most useful exercise turned out to be the plainest one: read other manufacturers’ published datasheets, divide the kilograms per hour by the airflow, and see where the numbers cluster. It takes ten minutes and it exposes quickly whether a quoted figure is realistic.

This article does that with datasheets from two European manufacturers, then shows how to convert a rating from one condition to another. The result is a rule of thumb you can use to sanity-check any quotation, ours included.

The short version

  • At 20 °C and 60% RH, the published RLZ series removes about 6.6 to 6.7 kg of water per hour for each 1,000 m³/h of dry air.[1]
  • The cold-and-dry ICE variant of the same range is lower, about 4.4 to 4.5 kg/h per 1,000 m³/h, because it is built for drier air.[2]
  • Capacity follows the water content of the entering air, not the RH. At 5 °C one datasheet shows capacity rising almost in step with moisture.[3]
  • Scaled to 27 °C and 60% RH with that relationship, the RLZ figure becomes roughly 9.9 kg/h per 1,000 m³/h. Treat that as an estimate, not a guarantee.

What the datasheets say

The two ranges below are published by their makers with the rating condition printed on the sheet. We have used only figures stated in the datasheets and computed the ratios ourselves.

RangeDry air flow (m³/h)Capacity (kg/h)kg/h per 1,000 m³/hRating condition
Seibu Giken-based RLZ series (DST)2,900 to 10,50019 to 706.6 to 6.720 °C / 60% RH, air density 1.20 kg/m³
RLZ ICE series (DST), for cold or dry duty4,500 to 12,00020 to 544.4 to 4.520 °C / 60% RH, air density 1.20 kg/m³

The RLZ sheet gives the range endpoints, and the ratio is almost constant from the smallest to the largest unit, which is what you would expect if the same rotor technology is scaled by size.[1] The ICE sheet describes the same cabinets tuned for very good capacity in dry or cold environments, and the ratio is lower because that duty gives the rotor less moisture to remove at a given airflow.[2]

A third manufacturer, Destech, publishes capacity at 20 °C and 60% RH of 102.6 kg/h for its MDC 18000, with an electrical connection of 165 kW for electric reactivation, or 15 kW when the reactivation heat comes from steam, water or gas.[3] The sheet gives no per-unit airflow in the figures we could retrieve, so we have not put that unit in the ratio column. We can still compute something from it: the electrical load per kilogram of water removed is 165 ÷ 102.6, about 1.6 kW for each kg/h at the rating condition. Most of that is the reactivation heater, which is why the same unit needs only 15 kW when the heat is supplied separately.

Capacity follows moisture, not relative humidity

The Destech sheet also prints capacity across a range of inlet humidity. At 5 °C it reads as follows, and we have added the humidity ratio of each row.

Inlet RH at 5 °CCapacity (kg/h)Water in the inlet air (g/kg)
50%50.82.7
60%60.93.2
70%70.93.8
80%80.04.3
90%89.04.9

Going from 60% to 90% RH raises the water in the inlet air by a factor of 1.5, and raises the capacity by a factor of 1.5. So capacity rises a little more slowly than the moisture available: the exponent that links them is about 0.9. That makes sense. A desiccant rotor leaves some water behind in the outlet air, so the extra moisture does not all convert into extra removal.

Converting a rating to your own condition

Moisture in the entering air is 8.7 g/kg at 20 °C and 60% RH, and 13.4 g/kg at 27 °C and 60% RH. Scale the 20 °C capacity by the ratio of those values raised to the exponent above and you get a multiplier of 1.5.

Worked example. Take the middle of the RLZ range, 6.6 kg/h per 1,000 m³/h at 20 °C and 60% RH. Multiplying by 1.5 gives about 9.9 kg/h per 1,000 m³/h at 27 °C and 60% RH. Our ND series is rated at 9.0 kg/h per 1,000 CMH at that condition, a little below this estimate. That is intentional: a rating should be a number a unit can meet, with the margin held back for rotor ageing and site variation.

This is an engineering estimate drawn from published sheets, not a measurement of any machine. Rotor depth, reactivation temperature and heat recovery all move the answer. But it is a good test. If a quotation promises 14 or 15 kg/h per 1,000 m³/h at a modest condition with a standard rotor, ask for the test report.

Questions to ask of any capacity figure

  • At what dry-bulb temperature and relative humidity, or humidity ratio, is the capacity quoted?
  • Is the airflow quoted for wet air or dry air, and at what density?
  • Is the capacity with electric, steam or gas reactivation, and does the unit include heat recovery?
  • What is the outlet dew point at that capacity? A high capacity with a high outlet dew point may not meet your target.
  • Is the figure a calculation or a tested value, and can you see the test?
  • If you are still deciding between desiccant and refrigerant equipment, start with our comparison of the two technologies.

Where this fits with NextAir

Our ND series covers 500 to 20,000 CMH in single units, with the full model table, the rating condition and the options on the desiccant dehumidifier manufacturer page. If you have a quotation from anyone that you want sanity-checked, send us the airflow, condition and capacity and we will tell you how it compares. For the power side of the picture, read where the power goes in a desiccant dehumidifier, and for the load you are trying to meet, how to calculate it.

Sources

  1. DST Svenska Gruppen (Seibu Giken rotors). Recusorb RLZ series datasheet.
  2. DST Svenska Gruppen. Recusorb RLZ ICE series datasheet.
  3. Destech (UAB Desiccant Technologies Group). Desiccant dehumidifier MDC 18000 technical datasheet.

Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.

Frequently Asked Questions

How many kg/h should a desiccant dehumidifier remove per 1,000 m³/h?

At 20 °C and 60% RH, published datasheets for two European ranges work out to roughly 4.4 to 6.7 kg/h per 1,000 m³/h, depending on the model and whether it is built for dry or cold duty.

Why do manufacturers quote capacity at 20 °C and 60% RH?

It is a convenient common reference. Capacity changes with the moisture in the inlet air, so the figure at your own site condition will differ, and you should ask for it.

Is a bigger kg/h figure always better?

No. Capacity at a given airflow also depends on the rotor, reactivation temperature and the outlet dew point you need. Check what dew point the capacity is delivered at.

Does heat recovery change capacity?

It mainly changes energy use. Recovering heat from the reactivation exhaust lowers the heater load per kilogram removed, as the 165 kW versus 15 kW figures on one datasheet show for different heat sources.

Can I use these ratios to size a dehumidifier?

Use them to check a quotation, not to size a unit. Sizing needs your moisture load, condition and target dew point.