How to Calculate the Moisture Load on a Dehumidifier
By the NextAir Systems engineering team. Last reviewed October 2026.
Most dehumidifier problems begin with one missing number: how many kilograms of water an hour the space actually gives up. Capacity is easy to read off a brochure. The load is the part someone has to calculate, and it is where over-optimistic assumptions do the damage.
The method is not complicated. You find how much air enters the space, how much more water that air carries than the air inside, and you multiply. Then you add anything wet that happens inside. We will do it for an ordinary warehouse and for a cold store, using conditions we state openly so you can swap in your own.
The short version
- Moisture load (kg/h) = mass flow of incoming air x the difference in humidity ratio between outside and inside air.
- A 8,000 m³ warehouse held at 25 °C and 45% RH, with outside air at 35 °C and 60% RH, takes about 58.7 kg/h of water for every half air change per hour.
- The leakage rate is the most uncertain input and usually the largest. Measure it, or size with a range, and never leave it at zero.
- Dehumidifier capacity is quoted at a rating condition. Convert your load to that condition, or ask for the capacity at yours.[1]
Step 1: write down the two air conditions
You need the inside condition you want to hold and the outside condition you want to survive. For the warehouse example we use 25 °C and 45% RH inside, which is a humidity ratio of 8.9 g/kg, and 35 °C and 60% RH outside, which is 21.4 g/kg. Convert both to humidity ratio. Relative humidity cannot be subtracted, because the two readings are at different temperatures, as we explain in the guide to dew point and relative humidity.
Step 2: find the airflow that enters the space
Air gets in three ways: mechanical ventilation, leakage through the envelope, and door openings. Ventilation is a number someone chose. Leakage and doors are estimates, and they are the ones that surprise people. Express them as air changes per hour so they scale with the room.
Step 3: multiply
The mass of dry air in a cubic metre at 25 °C is about 1.2 kg. For a 8,000 m³ warehouse, a range of leakage rates gives this:
| Air changes per hour | Air entering (m³/h) | Water brought in (kg/h) | Water brought in (litres/day) |
|---|---|---|---|
| 0.25 | 2,000 | 29.3 | 704 |
| 0.5 | 4,000 | 58.7 | 1,408 |
| 1.0 | 8,000 | 117.3 | 2,815 |
| 2.0 | 16,000 | 234.6 | 5,631 |
Worked example. At 0.5 air changes per hour the warehouse takes about 4,000 m³/h of outside air. Each kilogram of that air carries 12.6 g more water than the air inside, so the load is 58.7 kg/h. Over a 24-hour day that is about 1,408 litres. If the leakage were actually 1 air change per hour, the load would double. If a door is open to a loading bay for half the shift, it can be higher still.
A cold store is a different animal
Take a 3,600 m³ cold room held at 2 °C and 85% RH, with outside air at 32 °C and 70% RH. Assume 4 air changes a day through doors and leakage, which is an assumption and not a measurement. The room air carries 3.7 g/kg and the outside air 21.1 g/kg. The load is about 320 kg of water a day, or 13.3 kg/h. In an ordinary cold store that water does not stay as vapor. It freezes onto the evaporator and the floor, which is why the refrigeration plant spends so much energy on defrost. Removing it upstream is cheaper than freezing and melting it, a point we return to in the guide to condensation risk.
What else adds moisture
- Wet processes. Washdown, open water, drying and cooking release water you can weigh: measure how much water you use and how much leaves in drains and product.
- People. Small per person, but real in packing halls and offices. Take the figure from the occupancy standard that applies to you.
- Product and packaging. Hygroscopic materials give water back as the room dries, which can make a first pull-down take much longer than the steady load suggests.
- Wet floors and ponding. Evaporation from standing water can rival the leakage load. Fix the drains before sizing the plant.
Where the estimates go wrong
- Averaging the weather. Using the mean outdoor condition for the year hides the weeks that decide whether the room stays in specification.
- Treating leakage as zero. Even a new insulated building leaks, and dock doors and personnel doors dominate the number in working stores.
- Ignoring the first pull-down. Bringing a damp building down to target needs extra capacity for days or weeks, because the structure and stock release stored water.
- Mixing units. Humidity ratio in g/kg, vapor pressure in kPa and RH in percent get swapped in spreadsheets. Keep one basis, and sense-check the answer against litres per day.
- Forgetting the reactivation exhaust. A desiccant unit that draws its reactivation air from the same space adds to the leakage load. Duct it from outside where you can.
A useful sense-check for any result: a 1,000 m² store taking 20 kg/h of water is removing 480 litres a day, which is a lot of water for a building that is supposedly closed. If your answer looks like a flood, something in the leakage assumption deserves a second look, or the building has a wet process nobody mentioned.
Turning the load into a capacity
Dehumidifier capacity is rated at a stated inlet condition. European manufacturers commonly rate at 20 °C and 60% RH, with airflow quoted at a stated air density.[1] Warmer, wetter air gives higher capacity from the same unit, so a 20 °C rating understates what the machine does in a Gulf summer, and a hot, dry afternoon overstates it. Ask for capacity at your inlet condition, then add margin for pull-down and for the leakage uncertainty. Our own ND range is rated at 27 °C and 60% RH; the table of models is on the manufacturer page.
Where this fits with NextAir
Give us your space dimensions, target condition, outdoor design condition, door activity and any wet processes, and our team will run this calculation for your site and recommend a model or a bank of units. See also how the load changes by sector in our guidance for cold storage and warehouses, and our overview of desiccant versus refrigerant dehumidification.
Sources
- DST Svenska Gruppen (Seibu Giken rotors). Recusorb RLZ series datasheet.
- NOAA. Fast Facts: highest dew points and heat index.
Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.
Frequently Asked Questions
How do I calculate the moisture load for a dehumidifier?
Multiply the mass flow of air entering the space by the difference in humidity ratio between the outside air and the air you want inside, then add any water released by processes, people and wet surfaces.
What air change rate should I assume for leakage?
It depends on the building. A tight, well-sealed store may leak a fraction of an air change per hour, and an older building with frequent door use can leak several times that. Measure it with a blower-door or tracer-gas test if the answer matters, or size with a range.
Why is relative humidity no use in a load calculation?
Because the inside and outside readings are at different temperatures. Convert each to humidity ratio (grams of water per kilogram of dry air), then subtract.
Should I size the dehumidifier for the average or the peak load?
For the peak outdoor condition you must survive, plus a margin. An average-day selection is overloaded on the worst days, which are often the days that matter most.
Does a cold store need dehumidification if it already has refrigeration?
Moisture entering a cold store freezes on the evaporator and floor and is removed by defrost cycles. Drying the incoming air first reduces that load and the ice it causes, which is why desiccant units are common in low-temperature stores.