Humidity in Pharmaceutical Storage: What the ICH and WHO Climatic Zones Mean
By the NextAir Systems engineering team. Last reviewed October 2026.
Pharmaceutical humidity numbers get quoted loosely. People say a warehouse must hold 60% RH because they have seen 25 °C and 60% RH written on a stability protocol. The two are related but they are not the same thing, and a facility that confuses them can specify the wrong equipment for the wrong reason.
This article separates the three ideas that tend to get blended together: the climatic zones that define stability testing, the storage condition printed on a product’s label, and the condition your dehumidifier has to hold. We will be careful to say what we know and what you have to check against your own documents.
The short version
- ICH Q1A(R2), published in 2003, set the long-term stability conditions for zones I and II. For the hotter zones III and IV it left the definition to the regions and to WHO.[1]
- WHO split zone IV in October 2005 into IVa (30 °C / 65% RH) and IVb (30 °C / 75% RH).[1]
- India adopted 30 °C / 70% RH, Brazil approved the zone IVb conditions, and Russia and China accepted IVa.[1]
- Zone IVb conditions have a dew point of about 25.1 °C, nearly nine degrees above the dew point of a 22 °C, 50% RH store.
What the zones are for
The climatic zones are a way of deciding how a medicine should be tested before it is sold in a market. A product intended for a hot, humid country has to show it stays within specification when stored at conditions that reflect that climate. The zone sets the stability testing conditions. It is not a rule about how a pharmacy or warehouse must be conditioned.
The ICH guideline Q1A(R2) was introduced in 2003. It addressed the conditions for the temperate zones, and ICH agreed to leave the storage conditions for the hot zones III and IV to the individual regions and to WHO.[1] WHO then made its own change: in October 2005 its secretariat agreed to divide zone IV into IVa, hot and humid, and IVb, hot and very humid.[1]
| Condition | Temperature (°C) | RH (%) | Dew point (°C) | Water (g/kg dry air) |
|---|---|---|---|---|
| I, temperate (long-term 25 °C / 60% RH) | 25 | 60 | 16.7 | 11.9 |
| III, hot and dry | 30 | 35 | 12.9 | 9.3 |
| IVa, hot and humid | 30 | 65 | 22.7 | 17.4 |
| India’s adopted condition | 30 | 70 | 23.9 | 18.8 |
| IVb, hot and very humid | 30 | 75 | 25.1 | 20.2 |
| Accelerated testing, all zones | 40 | 75 | 34.7 | 36.0 |
The temperatures and humidities come from the published zone definitions as summarized in our sources.[1][2] The dew point and water content columns are our calculation, using standard psychrometric formulas at sea-level pressure. They matter because the dew point, not the RH, tells you how much water a dehumidifier has to remove, as we explain in the dew point guide.
Different markets, different conditions
National regulators did not all take the same path. India adopted 30 °C and 70% RH for long-term storage, Brazil approved the zone IVb conditions, and Russia and China accepted the zone IVa conditions.[1] A manufacturer who registers a product in several of these countries often runs the most demanding condition. The European Pharmaceutical Review analysis argues that acceptable stability at 30 °C and 75% RH can typically be used to predict acceptable stability at milder conditions, with caveats such as polymorphic changes and hydrate formation.[1]
For a facility in the Gulf, East Africa or India this explains why so many products on your shelf have been proven at conditions much wetter than your air-conditioned storage. It does not mean your storage may run at those conditions. The label does that job.
The three conditions people confuse
- The zone testing condition. Defined by ICH, WHO or the national regulator. It governs how the manufacturer tests the product.
- The label storage condition. Printed on the pack, often as a maximum temperature and sometimes a humidity limit. It is the legal and practical limit for storage.
- Your design condition. Set by your quality system, your validated warehouse mapping and the label, with margin. This is what you specify to the dehumidifier supplier.
What this means for equipment
Start from the label of the most demanding product you store, then add the margin your quality system requires, and give the supplier a temperature plus a dew point or humidity ratio. A store that must hold 25 °C and 60% RH sits at a dew point of about 16.7 °C, which a refrigerant coil can reach in most climates. A product with a tighter humidity limit, or a manufacturing room that must stay dry through a monsoon, moves the duty toward desiccant equipment. Our industry guidance for pharmaceutical facilities covers the specification points beyond the numbers.
What auditors tend to ask about
Whatever number you settle on, the paperwork usually matters as much as the equipment. Quality teams commonly expect a temperature and humidity mapping study of the store, calibrated sensors, defined alarm limits with a response procedure, and records that show the space stayed in range. A dehumidifier that cannot log its own performance, or that drifts without an alarm, creates work for the quality system even if the room is fine. Ask suppliers what data the unit records and how it reports a fault, and read our overview of dehumidifier technologies before comparing quotations.
We do not publish a single humidity target for pharmaceutical storage, because the right figure depends on your products and your regulator. If a number matters to a decision, confirm it against the current ICH and WHO texts and the product label.
Where this fits with NextAir
NextAir sizes dehumidifiers against the dew point and moisture load of the room, with the ND series covering 500 to 20,000 CMH and multi-unit banks above that. Tell our desiccant dehumidifier manufacturer team the label condition, space size, door activity and outdoor design condition, and we will recommend a configuration. For the load itself, see how to calculate moisture load.
Sources
- European Pharmaceutical Review. Towards global stability protocols: a decade of lost opportunities.
- ContractLaboratory.com. What are the different types of stability studies.
Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.
Frequently Asked Questions
What are the ICH stability zones?
They group the world's climates for stability testing. Zones I and II are temperate and subtropical, zone III is hot and dry, and zone IV is hot and humid, which WHO divided into IVa and IVb.
What is the difference between zone IVa and IVb?
Both are tested at 30 °C. Zone IVa uses 65% RH and zone IVb uses 75% RH.
Does zone IVb mean a warehouse can run at 75% RH?
No. The zone defines how a product is tested for stability. The label storage condition and your quality system define how the product must be stored.
Which condition did India adopt?
According to a European Pharmaceutical Review analysis, India adopted 30 °C and 70% RH, while Brazil approved the zone IVb conditions.
What dew point do the zone IVb conditions have?
About 25.1 °C, calculated at sea-level pressure. A 22 °C, 50% RH room has a dew point near 11 °C.