Planning Ethylene Media Change-Out: The Cumulative Load Over a Season
By the NextAir Systems engineering team. Last reviewed October 2026.
A scrubber’s media is a consumable, and like any consumable it needs a plan. The question is how many times a year it has to be changed, and the answer comes from adding up the ethylene the store makes and dividing by what the media can hold.
The first number is calculable. The second belongs to the media supplier, and it is the one you should insist on seeing. We work through the arithmetic with the capacity as a variable.
The short version
- A store of 100 t making an assumed 20 µL/kg·h for 6 months (4,380 hours) makes about 10.0 kg of ethylene.
- If the scrubber captures 90% of it and the media holds 5 g per kg, the season needs about 1,808 kg of media, around 2.9 changes of a 617 kg bed.
- Media capacity is a property of the media and the conditions, not a universal number. The 2, 5 and 10 g/kg used here are illustrations.
- A cold store makes less than the 20 °C rate used here, so real consumption is likely lower. Measure it.
The cumulative load
Take a store of 100 tonnes of a high-class fruit. We assume a rate of 20 µL/kg·h, inside the 10 to 100 range of that class,[1] running for 4,380 hours, which is six months. The total production is 20 × 100,000 × 4,380 = 8.76e+09 µL, which is 8,760 litres of ethylene. At about 1.15 µg per µL that is 10.0 kg.
That is the figure for the whole room at the textbook rate. Real production in a cold store will be lower, as explained in the temperature article, and it varies through the season with fruit maturity.
How much goes through the scrubber
Not all of the ethylene reaches the media. Some leaves with leakage and ventilation, and some of the fruit’s ethylene is absorbed by the fruit itself. In a sealed, well-circulated room most of it is carried to the scrubber, so we show two fractions, 50% and 90%, as bounds.
From ethylene to media
The media needed is the mass of ethylene captured divided by the capacity of the media in grams of ethylene per kilogram. Capacity depends on the media and the conditions, and the supplier should state it. The table uses three illustrative values. The last column divides by 617 kg, the mass of a bed with 1.23 m³ of media at 500 kg/m³, which is what a scrubber treating about 2,200 m³/h at 2 seconds of contact would hold.
| Assumed media capacity | Share of ethylene captured | Media needed for the season (kg) | Changes of a 617 kg bed |
|---|---|---|---|
| 2 g per kg | 50% | 2,511 | 4.1 |
| 2 g per kg | 90% | 4,520 | 7.3 |
| 5 g per kg | 50% | 1,004 | 1.6 |
| 5 g per kg | 90% | 1,808 | 2.9 |
| 10 g per kg | 50% | 502 | 0.8 |
| 10 g per kg | 90% | 904 | 1.5 |
Worked example. At 5 g/kg capacity and 90% capture, the season needs about 1,808 kg of media, which is 2.9 changes of the 617 kg bed. At 2 g/kg it is 7.3 changes, and at 10 g/kg 1.5. The spread is a factor of five. That is why the capacity is the one number to get in writing, with the conditions it applies to.
Turning it into a plan
- Estimate the seasonal production for your product at storage temperature, and the share that reaches the media.
- Get the media capacity from the supplier, with the temperature and humidity it is quoted at.
- Compute the changes per season and the cost, and schedule the first change before you expect to need it.
- Use an ethylene analyser on the outlet. When the outlet concentration rises toward the inlet, the media is spent.
- Log each change. After the first season you will have a measured consumption that beats any estimate.
A worked schedule
Suppose the supplier states 5 g of ethylene per kg of media and you expect 90% of the ethylene to reach it. The season needs about 1,808 kg, or 2.9 changes of the 617 kg bed. In practice that means one full change roughly every two months, with a first inspection a few weeks before. If the store is loaded progressively, the consumption in the first month is lower, so the first change can be later than the average suggests. If it is filled in a week and the fruit is at peak production, the first change comes sooner. The schedule is a working plan, adjusted by the outlet reading.
What to watch
- Humidity. Cold rooms are humid, and water on the media can lower its capacity. Ask the supplier how the media behaves at your RH.
- Dust and fruit debris, which block the bed and reduce the contact. Filter the air upstream.
- Peak periods. The load is concentrated in the weeks when the fruit is most active, so the media may be consumed unevenly through the season.
- Spent media handling. Treat it according to local waste rules and the supplier’s advice.
- Sizing and removal. The airflow depends on the target, as in the sizing example, and the bed on the contact time.
The value of keeping fruit is set out in the postharvest losses article, which is the other side of the same budget: the media is a cost, and the saved fruit is the return.
Where this fits with NextAir
NextAir’s ethylene scrubbers use media matched to the duty, and we state the expected change-out interval with its assumptions at the quotation stage. Send the product, tonnage, storage temperature and target to our ethylene scrubber manufacturer team. Our ethylene scrubber guide covers the technology, and bananas and tropical fruit describes a duty with different loading.
Sources
- TIS-GDV (German insurers’ transport information service). Allelopathy: ethylene production rates and sensitivity of fruit and vegetables.
- University of Florida IFAS (postharvest). Ethylene Treatments (presentation).
- A. A. Kader, Postharvest Technology of Horticultural Crops (Chapter 4), hosted by University of Florida IRREC. Postharvest Biology and Technology: an overview (Kader, ch. 4).
Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.
Frequently Asked Questions
How do I calculate ethylene scrubber media life?
Estimate the total ethylene the store makes over the season, take the share that reaches the media, and divide by the media's capacity in grams of ethylene per kilogram.
How much ethylene does a store make in a season?
For 100 t at an assumed 20 µL/kg·h for six months, about 10.0 kg. Real production in a cold store is likely lower.
What is the capacity of ethylene scrubber media?
It depends on the media and on temperature and humidity, so ask the supplier for it, with the conditions. The values in this article are illustrations.
How do I know when the media is spent?
Measure ethylene at the scrubber outlet. When the outlet concentration approaches the inlet, the media is exhausted.
Does humidity affect the media?
Often, yes. Cold stores run at high humidity, so ask how the media performs at your RH.