How to Size Ethylene Removal for a Storage Room: A Worked Example
By the NextAir Systems engineering team. Last reviewed October 2026.
Ethylene scrubber sizing starts from two numbers that nobody in the store has written down: how much ethylene the product makes, and how low it has to be held. Once you have both, the airflow is one division. The target concentration is the assumption that moves the answer by a factor of fifty, so this guide spends most of its time on it.
We work an example for a store of pears and compare the scrubber with ventilation using fresh air, which is the alternative people usually think of first.
The short version
- A store of 100 t of pears at an assumed 20 µL/kg·h makes 2,000,000 µL of ethylene an hour, about 2.3 g/h.
- To hold 1 ppm with a scrubber removing 90% per pass needs about 2,222 m³/h through the scrubber. Holding 0.1 ppm needs about 22,222 m³/h.
- Ventilating with outside air to hold the same 1 ppm needs about 2,000 m³/h, a similar volume, but every cubic metre has to be cooled and dried.
- The right target depends on the crop’s sensitivity, which you should take from the postharvest literature for your variety.[1]
The mass balance
At steady state, the ethylene the product makes equals the ethylene leaving the room. With a scrubber, the ethylene removed per hour is the airflow through it times the concentration times the fraction removed per pass. So the airflow needed is:
- Q = E ÷ (η × C)
- E is the production in µL/h, η is the per-pass removal efficiency (as a fraction), and C is the target concentration in µL/L, which is ppm.
- With E in µL/h and C in ppm, Q comes out in litres per hour. Divide by 1,000 for m³/h.
For 100 t of pears, we assume 20 µL/kg·h, which lies inside the high class of 10 to 100.[2] That gives E = 20 × 100,000 = 2,000,000 µL/h. The rate is an assumption: look up your cultivar, and remember that production in a cold store is lower than the 20 °C figure.[3]
The target decides the answer
| Target ethylene (ppm) | Scrubber airflow at 90% per pass (m³/h) | In thousands of m³/h | Air changes per hour in a 2,000 m³ room |
|---|---|---|---|
| 0.1 | 22,222 | 22.2 | 11.11 |
| 0.5 | 4,444 | 4.4 | 2.22 |
| 1.0 | 2,222 | 2.2 | 1.11 |
| 5.0 | 444 | 0.4 | 0.22 |
Worked example. Holding 1 ppm needs 2,222 m³/h. Holding 0.1 ppm needs 22,222 m³/h, ten times more, because at a lower concentration each cubic metre carries less ethylene. A scrubber that is perfectly adequate for a 1 ppm target will not hold 0.1 ppm. Before you buy, ask the product specialist what the crop needs, and write the number in the specification.
Why not just ventilate?
Fresh-air ventilation removes ethylene by dilution. The airflow for the same target is E ÷ C, with no efficiency factor, since the outside air is assumed to be free of ethylene.
| Target (ppm) | Fresh air needed (m³/h) |
|---|---|
| 0.1 | 20,000 |
| 0.5 | 4,000 |
| 1.0 | 2,000 |
| 5.0 | 400 |
The fresh air figure is only about 10% below the scrubber’s, so on volume alone they look alike. The difference is thermal. The scrubber recirculates air already at store temperature. The ventilation brings in warm outdoor air that the refrigeration plant must cool, and in a hot climate that load can be larger than all the other loads in the room put together. Ventilation is also a way to bring in humidity, which the dehumidification articles on this site explain the cost of, as in the moisture load guide.
A second example: the sensitive neighbour
Sizing is not only about the producer. If sensitive produce shares the room, the target concentration is set by the most sensitive crop, and that can pull the whole duty down by an order of magnitude. A store of 100 t of pears with no sensitive neighbours might be content at 1 ppm. Put a few pallets of a sensitive vegetable in the same space and the target may fall to 0.1 ppm, which in the table above means ten times the airflow. Often the cheaper answer is to give the sensitive crop its own small room with its own removal, and let the large producer run at the higher target. The reasoning behind the choice is in the mixed loads guide.
What else goes in the calculation
- Per-pass efficiency. It depends on the media, bed depth and contact time, and falls as the media loads. Use the supplier’s figure at the end of the interval, not at the start.
- Mixing. The scrubber only sees the air that reaches it. Poor circulation leaves pockets of high concentration.
- Loading pattern. The store is full at peak, and the rate depends on maturity. Size for the peak.
- CA and atmosphere. Controlled atmosphere storage suppresses production, as the low-oxygen work at UC Davis shows,[4] and the scrubber then carries a lighter duty.
- Media life. The mass of ethylene captured sets the change-out, as in the change-out article.
Where this fits with NextAir
NextAir builds ethylene scrubbers of 1,200 to 30,000 CMH, horizontal or vertical, with multi-bank systems above that. Send the product, tonnage, room volume and target concentration to our ethylene scrubber manufacturer team and we will size the airflow and the media. Our ethylene scrubber guide covers ripening and removal, and mixed produce distribution shows the harder case.
Sources
- A. A. Kader, Postharvest Technology of Horticultural Crops (Chapter 4), hosted by University of Florida IRREC. Postharvest Biology and Technology: an overview (Kader, ch. 4).
- TIS-GDV (German insurers’ transport information service). Allelopathy: ethylene production rates and sensitivity of fruit and vegetables.
- University of Florida IFAS (postharvest). Ethylene Treatments (presentation).
- J. R. Gorny and A. A. Kader, UC Davis, 1997. Low Oxygen and Elevated Carbon Dioxide Atmospheres Inhibit Ethylene Biosynthesis in Preclimacteric and Climacteric Apple Fruit.
Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.
Frequently Asked Questions
How do I size an ethylene scrubber?
Divide the ethylene production in µL/h by the per-pass efficiency times the target concentration in ppm. The result, divided by 1,000, is the airflow in m³/h.
What ethylene concentration should I aim for?
It depends on how sensitive the commodity is. Take the number from the postharvest literature for your variety, and write it into the specification.
Why is a scrubber better than ventilation?
Because it recirculates air already at store temperature. Fresh air ventilation brings in a heat and moisture load that the refrigeration plant must remove.
Does the number of air changes matter?
It is a useful check, but the airflow you need comes from the production and the target. A room with a low-producing crop needs far fewer.
What per-pass efficiency should I assume?
Use the supplier's stated value at the end of the media interval. A new bed will do better, and an exhausted one worse.
Talk to Our Engineering Team
Call +91-9311805618 or use our contact form for a facility-specific recommendation.