The Arithmetic of Odour Dilution: How Much Clean Air Would It Take?
By the NextAir Systems engineering team. Last reviewed October 2026.
There is a tempting shortcut for an odour problem: make the exhaust taller, add a fan, push more air through. Dilution does work. The trouble is the size of the numbers, and they are easy to calculate on the back of an envelope once you have an odour concentration in European odour units.
This guide does that arithmetic. It will not replace a dispersion model, which accounts for the stack, weather and terrain, but it shows the scale of the dilution required and what the same job looks like as a removal efficiency.
The short version
- Dilution factor = odour concentration ÷ target. A 2,000 ouE/m³ source diluted to a 5 ouE/m³ target needs a 400:1 dilution.[1]
- For a 5,000 m³/h source at 2,000 ouE/m³, reaching 5 ouE/m³ by dilution alone needs about 2,000,000 m³/h of clean air, which is 556 m³/s.
- The same job done by treatment needs a removal efficiency of 1 minus target over concentration: 99.75% in this example.
- Real dispersion is not simple dilution. Weather, stack height and building wake change the answer, and a specialist model should set the final target.
Dilution is a ratio
In the European system an odour concentration is the dilution factor needed to reach the detection threshold.[1] A source at 2,000 ouE/m³ must be diluted 2,000 times before a panel can only just detect it. If a regulator, a consultant or a customer names a target at the receptor, the dilution that has to happen between the stack and the receptor is simply the concentration divided by the target.
For example, a source at 2,000 ouE/m³ and a target of 5 ouE/m³ needs 400:1. For every cubic metre of exhaust there must be 399 cubic metres of clean air mixed in before the air reaches the receptor. The atmosphere does that job for free when the stack is tall and the wind is up. It does it badly when the air is still, which is often the hour residents notice the smell.
What it looks like as numbers
The table covers a 5,000 m³/h source at three strengths and three illustrative targets. The targets are arithmetic choices, not regulatory limits. Clean air required is the dilution ratio times the source flow.
| Source flow (m³/h) | Source (ouE/m³) | Target (ouE/m³) | Dilution ratio | Clean air needed (m³/h) | Equivalent removal efficiency |
|---|---|---|---|---|---|
| 5,000 | 500 | 1 | 500 | 2,500,000 | 99.8% |
| 5,000 | 500 | 5 | 100 | 500,000 | 99.0% |
| 5,000 | 500 | 10 | 50 | 250,000 | 98.0% |
| 5,000 | 2,000 | 1 | 2,000 | 10,000,000 | 100.0% |
| 5,000 | 2,000 | 5 | 400 | 2,000,000 | 99.8% |
| 5,000 | 2,000 | 10 | 200 | 1,000,000 | 99.5% |
| 5,000 | 10,000 | 1 | 10,000 | 50,000,000 | 100.0% |
| 5,000 | 10,000 | 5 | 2,000 | 10,000,000 | 100.0% |
| 5,000 | 10,000 | 10 | 1,000 | 5,000,000 | 99.9% |
The right-hand column is the useful one. The same dilution that would need millions of cubic metres of air per hour can be achieved by treatment with an efficiency of 99.5% or 99.9%. That is the real choice: accept the dilution the atmosphere gives you and hope, or take the odour out of the exhaust.
Why you cannot just add a fan
Worked example. A 5,000 m³/h exhaust at 2,000 ouE/m³ with a 5 ouE/m³ target needs 400:1. To achieve that with a fan in the duct you would add 1,995,000 m³/h of fresh air, about 80 times the original flow, and the fan power rises with it. You would also have to do it at the moment of worst atmospheric conditions. The cost of moving the air exceeds the cost of treating the original 5,000 m³/h.
Taller stacks help by placing the plume higher where there is more turbulence and by raising the release height, but the benefit has limits. A stack that clears the building wake is part of every good odour design, and it is a complement to treatment, not a substitute.
How treatment efficiency is set
- Start from the emission rate, concentration × flow, as in our guide to reading an odour survey.
- Set the target at the receptor with a dispersion model, then work back to a stack concentration.
- Convert the stack concentration to a removal efficiency: 1 minus target over source.
- Check whether a single bed can deliver it. Efficiencies above 99% usually need a second stage, a longer contact time, or both.
- Plan monitoring, because an odour system that is not monitored cannot demonstrate that it is working.
If the numbers show a high flow and a modest concentration, treat the flow first. Reducing the volume you have to treat by capturing the source tightly can cut the equipment size dramatically, as we show with a worked example in capture at source.
Where to start
Before choosing any technology, collect three numbers: the odour or H₂S concentration at the source over a representative period, the true airflow, and the target the receptor will accept. With those three you can compute the dilution, the emission rate and the efficiency in a few minutes, and you will know whether you are looking at a small, concentrated problem or a large, dilute one. The two call for different equipment, and mixing them up is the commonest reason odour projects are over- or under-built.
Mixed odours and the limits of the arithmetic
Odour units are for mixtures, and treatment efficiency for a mixture is not a single number. A bed can remove hydrogen sulfide extremely well and let a trace of a mercaptan through, and since mercaptans have very low thresholds, the odour concentration at the outlet may be dominated by the compound the bed handled worst. This is why chemical analysis should accompany olfactometry, and why the media in an odour adsorber is chosen for a list of compounds and not a single one.
Where this fits with NextAir
Give our odor control adsorber manufacturer team the source flow, the odour or H₂S concentration and the outlet target, and we will propose a single or two-stage design. Our dry odor control adsorber guide explains the technology, and waste management and landfills and chemical processing show where the numbers get large.
Sources
- CEN (EN 13725:2022), via EVS. EN 13725:2022 Stationary source emissions: determination of odour concentration by dynamic olfactometry and odour emission rate.
- US OSHA. Hydrogen Sulfide: Hazards.
Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.
Frequently Asked Questions
How do I calculate the dilution needed for an odour?
Divide the odour concentration by the target concentration. A 2,000 ouE/m³ source and a 5 ouE/m³ target need a 400:1 dilution.
Is dilution a good way to control odour?
It is rarely a practical sole solution. The volume of air required is usually many times the exhaust flow, and atmospheric dilution varies with the weather.
What removal efficiency is equivalent to a dilution ratio?
One minus the inverse of the ratio. A 400:1 dilution equals 99.75% removal.
Does a taller stack solve an odour problem?
It helps disperse the plume and can avoid building wake effects, but it does not reduce the emission. It works best alongside treatment.
Why does the odour persist after hydrogen sulfide is removed?
Because other compounds, especially mercaptans, have very low odour thresholds. The outlet odour is often controlled by the compound the bed removes least well.