Legionella Risk in Evaporative Systems: What ASHRAE 188 Asks of Air Washer Owners
By the NextAir Systems engineering team. Last reviewed October 2026.
An air washer is a recirculating water system with a fan attached. The water sits in a sump, runs through sprays or over media, and leaves some of itself in the airstream as droplets and fine mist. Those are the ingredients every water-safety standard worries about. It does not mean air washers are unsafe. It means the water has to be managed deliberately, and a well-designed washer makes that easy.
This article summarises what ASHRAE Standard 188 requires, in plain terms, and turns it into design and operating practice for an air washer. It is an engineering summary and not legal advice, so check the rules that apply where you operate.
The short version
- ASHRAE Standard 188, Legionellosis: Risk Management for Building Water Systems, first published in 2015 and updated in 2018 and 2021, is a voluntary consensus standard that sets minimum risk management requirements.[1]
- It asks owners to survey for components that can aerosolize water and to write a water management plan for specified non-potable systems. The standard gives the framework and the owner chooses the detailed measures.[1]
- Some jurisdictions have made it a legal duty: New York, for example, requires owners of buildings with cooling towers to have a maintenance programme and plan developed in accordance with the standard.[2]
- Good design reduces the work: smooth, drainable sumps, effective drift eliminators, accessible components and the ability to drain and dry the system.
Why a washer is on the list
Legionella bacteria are common in natural water and survive in engineered systems under the right conditions: warm water, stagnation, biofilm and nutrients. The disease they cause, legionellosis, is spread by breathing in fine droplets, so the systems of concern are the ones that make an aerosol. ASHRAE 188 asks building managers to survey for water system components that can aerosolize contaminated water, and for risk factors including building size and occupant health.[1] A washer’s spray chamber and drift path are exactly that kind of component.
What the standard asks for
The standard sets out minimum requirements for the design, construction, commissioning, operation, maintenance and expansion of building water systems.[2] In outline, an owner must identify the systems, write a plan and run it. The plan’s required components are in the standard itself, which you should read. Here is the structure in plain terms, drawn from the published summaries:
| Step | What it involves |
|---|---|
| Survey | Identify the components that can aerosolize water, such as sprays, wet media and drift paths, and any factors that raise risk, such as building size and occupant vulnerability |
| Plan | Write a water management plan covering the systems identified, with the detailed measures chosen by the owner within the standard’s framework |
| Control | Define control measures, limits and monitoring for each system, and what to do when a limit is exceeded |
| Verify and document | Confirm the programme works, keep records, and review it when conditions change |
ASHRAE Guideline 12, updated in 2020 and again in 2023 with new guidance on temperature control and supplemental disinfection, gives practical direction on implementing the standard.[1] Some regulators go further: New York requires a maintenance programme and plan for each cooling tower built to Standard 188, and the US CDC lists the standard among its guidance documents.[2]
Design features that make management easier
- A sump that drains completely, with a sloped floor and a drain at the lowest point, so no pockets hold stagnant water.
- Smooth, corrosion-resistant materials, such as stainless steel, that are easy to clean and give biofilm little to hold on to. Our units use stainless steel construction for this reason.
- Effective drift eliminators, because every droplet that escapes the airstream is a droplet that carries whatever is in the water.
- Access to every wetted surface, so inspection and cleaning are possible without a long shutdown.
- Make-up and bleed that keep the water turning over, as in the water consumption article.
- Provision for monitoring, such as conductivity and temperature sensors, and sample points for microbiological testing.
Stagnation: the number to watch
The risk rises when water sits still. One way to see it is the turnover time, the sump volume divided by the make-up flow. A larger sump with a low make-up rate takes a long time to replace its water.
| Sump volume (m³) | Make-up (litres/hour) | Time to replace one sump volume (hours) |
|---|---|---|
| 1 | 60 | 16.7 |
| 1 | 91 | 11.0 |
| 3 | 60 | 50.0 |
| 3 | 91 | 33.0 |
| 6 | 60 | 100.0 |
| 6 | 91 | 65.9 |
A 6 m³ sump on 60 litres an hour of make-up takes about 100 hours, over four days, to turn over. When the washer is idle, which is common in a seasonal climate, the water does not turn over at all. The make-up figures here are illustrative, drawn from our water consumption calculation. The practical rules that follow are to size the sump for the duty and not more, drain and dry the system when it will be idle for an extended period, and restart with a clean-and-disinfect routine.
Operating practice
- Write the water management plan before commissioning and keep it with the equipment.
- Record water temperature, conductivity and treatment dosing on a schedule you can defend.
- Inspect the sump, eliminators and spray bank at set intervals, and clean when you find deposits.
- Disinfect before the first start, after any shutdown, and after any significant contamination, using a method your water treatment provider supports.
- Test according to the plan and act on results, with a defined response when a limit is exceeded.
- Review the plan after any change to the system, the building or the occupants.
Cooling coil condensate drain pans are a separate but related water source, discussed in the condensate article.
Where this fits with NextAir
NextAir builds air washers in stainless steel with fully drainable sumps, eliminators and access doors, and can supply conductivity-controlled bleed. We do not provide legal or microbiological advice, so involve your water treatment specialist and check local rules. Send your application to our industrial air washer manufacturer team, and see our air washer guide and the energy picture in the energy comparison.
Sources
- Environmental Law Institute. Legionella Management in Building Water Systems: summary of ASHRAE Standard 188.
- ASHRAE. Standard 188-2021 fact sheet.
Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.
Frequently Asked Questions
Does ASHRAE 188 apply to air washers?
The standard applies to building water systems and asks owners to survey for components that can aerosolize water. A spray chamber with a drift path falls within the type of component it describes, but check how the standard and local law apply to your installation.
Is ASHRAE 188 mandatory?
It is a voluntary consensus standard, but some jurisdictions, such as New York for cooling towers, require plans developed in accordance with it.
What is a water management plan?
A documented programme that identifies the water systems, sets control measures and limits, defines monitoring and records, and says what to do when something goes wrong.
How do I reduce Legionella risk in an air washer?
Design for full drainage and cleaning, use effective drift eliminators, keep water turning over, monitor and treat the water, and drain and disinfect after idle periods.
Does an idle air washer carry more risk?
Standing water is the main concern. If the system will be idle for a long time, drain and dry it, and clean and disinfect before restarting.