Cooling Coil Condensate: How Much Water Does an AHU Make?
By the NextAir Systems engineering team. Last reviewed October 2026.
A cooling coil in a humid climate is a small water factory. The water is clean, it is made continuously, and in many buildings it runs to a drain and is forgotten until the trap overflows. How much there is can be calculated in one line, and the answer is usually larger than people expect.
This guide does that calculation for a 10,000 m³/h unit across a range of humidity, then covers drain design and the uses of the water.
The short version
- A 10,000 m³/h unit cooling 35 °C air to 13 °C and 95% RH condenses about 99 kg/h at 50% RH entering, and about 220 kg/h at 80% RH. That is up to 5,271 litres a day.
- Over 3,000 hours of humid operation, the unit makes around 659 m³ of water.
- The condensate is nearly pure, so it can be reused, but check for contaminants picked up from the coil.
- The drain trap must seal against the fan’s pressure, and a blocked drain is a common cause of leaks and microbial growth.
The calculation
Condensate is the water the air loses between the coil’s entry and exit. Mass of water per hour = dry air mass flow × (entering humidity ratio − leaving humidity ratio). If the entering air has a dew point below the leaving temperature, nothing condenses. If it is above, the difference is condensed.
The table cools 10,000 m³/h from 35 °C at different relative humidities to 13 °C at 95% RH (8.9 g/kg). The last column is the water made over 3,000 hours, in cubic metres, which is a plausible humid-season operating period for a Gulf building.
| Entering RH at 35 °C | Entering dew point (°C) | Entering water (g/kg) | Leaving water (g/kg) | Condensate (kg/h) | Condensate (litres/day) | Over 3,000 h (m³) |
|---|---|---|---|---|---|---|
| 30% | 14.8 | 10.5 | 8.9 | 19 | 454 | 56.8 |
| 50% | 23.0 | 17.8 | 8.9 | 99 | 2,381 | 297.6 |
| 70% | 28.7 | 25.2 | 8.9 | 179 | 4,307 | 538.4 |
| 80% | 31.0 | 28.9 | 8.9 | 220 | 5,271 | 658.8 |
Worked example. At 80% RH the air carries 28.9 g/kg and leaves at 8.9 g/kg. The difference of about 20.0 g/kg across roughly 10,946 kg/h of dry air is 220 kg/h of water, which is 5,271 litres a day from one air handling unit. A building with twenty such units makes about 105 m³ a day in this weather.
The drain
Condensate drains by gravity from the coil’s drain pan, through a trap, to a waste line. The trap is more than a smell barrier. In a draw-through unit the fan sits downstream of the coil, so the coil section is under negative pressure, and without a deep enough water seal the fan pulls air up the drain and holds water in the pan, which overflows into the casing. The principle is that the water seal depth must exceed the negative pressure in the coil section, expressed as a height of water. As a rough conversion, 100 Pa is about 10 mm of water, so a coil section at −600 Pa needs a seal of well over 60 mm, plus the manufacturer’s margin.
- Match the trap to the pressure, not to the pipe size. Ask for the coil section pressure at design and at dirty-filter condition.
- Slope the pan so it drains completely. Standing water grows biofilm.
- Keep the trap primed in dry weather. A trap that dries out lets air bypass the seal.
- Provide access to clean the pan and trap. Many problems are a trap blocked with dust.
- Add a pan overflow switch on critical installations.
Water standing in a drain pan is a contamination route in any evaporative or cooling system. The wider risk of Legionella in water systems is covered in Legionella risk and ASHRAE 188.
What it means for the design
The condensate rate is a direct readout of the latent load, so it is also a check on your coil calculation. If the unit makes far more water than the table suggests, the outdoor air fraction or the infiltration is higher than assumed, as the load method in from cooling load to AHU airflow shows. If it makes far less, the coil may not be reaching the dew point you need. Recovery wheels also change the picture, because an enthalpy wheel removes moisture before the air reaches the coil, cutting both the load and the condensate, as quantified in energy recovery in hot, humid climates.
Using the water
Coil condensate is close to distilled water. It contains little dissolved mineral, though it picks up dust, metals from the coil and some microbes. After simple filtration and, where needed, disinfection it is suitable for non-potable uses where the low mineral content helps: cooling tower and evaporative cooler make-up, irrigation, flushing and washdown. The make-up demand of an air washer is a natural match, and we quantify it in air washer water consumption.
- Collect from several units into a tank, with a first-flush diverter.
- Treat to the standard the use needs. Do not use for potable supply without full treatment and approval.
- Size from the table: tens to hundreds of litres an hour per unit in humid weather, and none in dry weather.
- Check the economics. Where water is expensive or limited, as in many Gulf locations, the payback can be short.
Where this fits with NextAir
NextAir’s AHUs have sloped stainless steel or coated drain pans with condensate connections sized for the coil duty, and we state the coil section pressure so the trap can be designed. Send the airflow and design humidity to our air handling unit manufacturer team. See coil selection for the load and the AHU guide for the unit, and the food and beverage page for hygiene-sensitive drains.
Sources
- NOAA. Fast Facts: highest dew points and heat index.
- Guinness World Records. Highest dewpoint temperature.
Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.
Frequently Asked Questions
How much condensate does a cooling coil make?
A 10,000 m³/h unit cooling air from 35 °C to 13 °C can make about 99 kg/h at 50% RH entering and about 220 kg/h at 80% RH.
How do I calculate condensate from a cooling coil?
Multiply the dry air mass flow by the difference in humidity ratio between the entering and leaving air.
Why does the drain trap need to be deep?
In a draw-through unit the coil section is under negative pressure, and the water seal must be deeper than that pressure expressed as a water height, or air will be pulled up the drain.
Can coil condensate be reused?
Yes, for non-potable uses such as cooling tower make-up, irrigation and washdown, after filtration and any required disinfection. It is not suitable as drinking water without full treatment.
What causes a drain pan to overflow?
A blocked drain, a trap that is too shallow for the coil section pressure, a pan that does not slope, or condensate production above what the drain was sized for.