Cooling Coil Selection: Why Enthalpy, Not Dry-Bulb Temperature, Sizes the Coil

By the NextAir Systems engineering team. Last reviewed October 2026.

Walk into a plant room in a humid climate and ask how the cooling coil was sized, and the answer is often a dry-bulb temperature: it gets to 40 or 45 in summer, so we sized for that. The coil does not know the dry-bulb temperature. It sees the energy in the air, and that depends as much on how much water the air carries as on how hot it is.

This guide does the arithmetic on a simple case, shows the sensible and latent split, and explains why the wettest day, not the hottest, usually sets the size of the coil.

The short version

  • For 10,000 m³/h cooled from 35 °C to 13 °C at 95% RH, the coil load is about 56 kW when the entering air is at 20% RH and 225 kW at 80% RH. The dry-bulb temperature is identical.
  • The sensible heat ratio falls from 1.27 to 0.32 as the air gets wetter, so most of the extra load is latent: condensing water.
  • A coil sized on dry-bulb temperature alone is too small on the humid day and too large on the dry one. Use the design wet-bulb or enthalpy.
  • Dew points as high as 35 °C have been recorded on the Gulf coast, so the humid case is not hypothetical.[1][2]

What the coil actually removes

A cooling coil takes energy out of the air in two forms. Sensible heat is the energy that changes the temperature. Latent heat is the energy released when water vapor condenses onto the coil. Both come out of the same chilled water, and both must be counted when the coil is sized. The total is the mass flow of dry air multiplied by the change in enthalpy.

  • Total load (kW) = dry air mass flow (kg/s) × (h entering − h leaving) in kJ/kg
  • Sensible load = mass flow × specific heat × temperature change
  • Latent load = total − sensible
  • Sensible heat ratio (SHR) = sensible ÷ total

Same temperature, different load

Take 10,000 m³/h of air at 35 °C and cool it to 13 °C and 95% RH, which is a typical coil leaving condition. Now change only the entering humidity.

Entering RH at 35 °CWet-bulb (°C)Dew point (°C)Water (g/kg)Enthalpy (kJ/kg)Total load (kW)Sensible (kW)Latent (kW)SHR
20%18.98.77.053.15671-151.27
40%23.919.414.171.511271410.63
60%28.226.121.490.216971980.42
80%31.831.028.9109.4225711540.32

At 20% RH the dew point is 8.7 °C, below the coil’s leaving temperature, so almost nothing condenses and the load is nearly all sensible. At 80% RH the dew point is 31.0 °C and the air carries 28.9 g of water per kilogram, so the coil spends most of its capacity condensing it. The total load is 4.0 times larger for the same dry-bulb temperature.

Worked example. A designer sizes the coil for 35 °C, and has the 40% RH column in mind: 112 kW. On a humid day at 80% RH the load is 225 kW, which is 101% more than the coil can supply. The result is warm, damp supply air. The room temperature may hold, but humidity drifts up, and that is the complaint: clammy, not hot.

Why humid climates are hard on coils

The highest dew point ever recorded was 35 °C at Dhahran, Saudi Arabia, on 8 July 2003, with a dry-bulb temperature of 42 °C.[1][2] That is a record, not a design condition, but it tells you how much latent load the Gulf can present when the weather turns. Our guide to air handling units explains why standard coils designed for temperate climates struggle there, and our dew point guide covers the moisture side in more depth.

Part load is where humidity is lost

Coils are sized for the peak, but they spend most of the year at part load. When the chilled water valve closes down to hold temperature, the coil surface warms, and the air leaves with more moisture than at design. In a humid climate that is exactly the situation in which the building starts to feel damp at night, when the sensible load has gone and the latent load has not. Face-and-bypass dampers, variable-speed fans that slow the airflow across the coil, or reheat fed from recovered heat all keep the coil cold enough to condense. Ask how the unit holds the leaving dew point at 30% and 50% of the sensible load, not just at 100%.

How to specify it

  • Give the design wet-bulb or humidity ratio as well as the dry-bulb. Ask the supplier to size the coil on both and state which governs.
  • State the required leaving condition, both temperature and humidity. A coil that meets 13 °C may not meet 95% RH, or the room dew point you need.
  • State the chilled water temperatures. Supply and return set the coil’s ability to dehumidify. A coil cannot dry air below the temperature of its own surface.
  • Ask for the sensible heat ratio at design and at part load. A low SHR means the coil is doing a lot of dehumidification and the plant should be sized for it.
  • Check part-load behaviour. Many coils dehumidify poorly when the chilled water valve is throttled. A face-and-bypass or reheat arrangement can control humidity when the sensible load falls.

The next step, turning the load into airflow and the airflow into a unit size, is covered in from cooling load to AHU airflow, and what happens to all that condensed water is in how much water an AHU makes.

Where this fits with NextAir

NextAir manufactures air handling units from 1,000 to 30,000 CMH as a single unit, with multi-unit arrangements above that and custom designs beyond 200,000 CMH. Our coils are selected on the design wet-bulb and the leaving condition you need. Send those with the airflow to our air handling unit manufacturer team. Regional conditions are covered on our pages for the UAE and Saudi Arabia.

Sources

  1. NOAA. Fast Facts: highest dew points and heat index.
  2. Guinness World Records. Highest dewpoint temperature.

Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.

Frequently Asked Questions

Why is a cooling coil sized on enthalpy rather than dry-bulb temperature?

Because the coil removes both the heat that changes temperature and the heat released when water condenses. The second part depends on the humidity, which the dry-bulb temperature does not show.

What is sensible heat ratio?

The share of the coil's total load that is sensible heat. A low value means more of the load is latent, from dehumidification.

What is the design wet-bulb temperature?

The wet-bulb temperature that a given percentage of hours in a year do not exceed. It is the usual basis for sizing cooling coils and cooling equipment.

Can a chilled water coil dry air to any dew point?

No. It cannot dry air below its own surface temperature, so the chilled water temperature limits the dew point it can reach.

Why does my air conditioning feel clammy?

Often because the coil is sized or controlled for the sensible load alone, so on humid days it cools the air without removing enough water.