Energy Comparison: Air Washer Versus Direct Expansion and Chilled Water, per 1,000 m³/h

By the NextAir Systems engineering team. Last reviewed October 2026.

The usual claim is that evaporative cooling uses a fraction of the energy of refrigeration, and it is true. How large a fraction depends on the weather, because the cooling the washer delivers depends on the wet-bulb depression while its fan and pump power barely change.

We calculate it for 1,000 m³/h across three conditions. The inputs are assumptions and are written down, so you can substitute your own. The comparison also comes with a caveat that decides many projects: the two do not give you the same air.

The short version

  • At 42 °C and 20% RH, an air washer delivers about 5.0 kW of sensible cooling per 1,000 m³/h for roughly 0.11 kW of fan and pump power, which is 47.2 kW of cooling per kW of electricity. A DX unit at an assumed COP of 3 would use 1.66 kW.
  • At 35 °C and 70% RH the washer delivers only 1.4 kW, so its advantage shrinks to 12.8 kW of cooling per kW of electricity.
  • Refrigeration also dehumidifies. An air washer raises humidity. If the humidity matters, the comparison is not like for like.
  • DOE guidance on fan systems cautions against decisions based on lowest first cost rather than life-cycle cost, and this is such a case.[1]

The assumptions

  • Airflow 1,000 m³/h.
  • Air washer at 85% saturation efficiency, with an air-side pressure drop of 120 Pa at 60% fan efficiency, and a spray pump of 0.05 kW per 1,000 m³/h. These are illustrative numbers.
  • Direct expansion cooling at a coefficient of performance (COP) of 3, and chilled water at 5, both counting the whole plant. Real COPs vary with the equipment and the load, so replace these.
  • Equal sensible cooling: each system is credited with the same kilowatts of sensible heat removed from the air.

The result

ConditionWasher supply (°C)Sensible cooling (kW per 1,000 m³/h)Washer electricity (kW)kW cooling per kW electricityDX electricity at COP 3 (kW)Chilled water at COP 5 (kW)Washer power as % of cooling
40 °C, 30% RH27.34.00.1137.91.330.802.6
42 °C, 20% RH26.15.00.1147.21.661.002.1
35 °C, 70% RH30.81.40.1112.80.450.277.8

Worked example. At 42 °C and 20% RH the washer cools 1,000 m³/h by about 15.8 K for 0.11 kW. A DX unit delivering the same 5.0 kW needs 1.66 kW, about 15 times as much. Over 3,000 hours at USD 0.10 per kWh, that is USD 33 for the washer against USD 498 for DX, per 1,000 m³/h. A plant moving 50,000 m³/h multiplies both by 50.

At 35 °C and 70% RH, the washer delivers only 1.4 kW per 1,000 m³/h, so the same fan and pump power buys far less cooling. Its advantage over chilled water falls from 9 times to 2 times. It is still lower in this model, but the supply air is at about 94% RH, and the saving is bought with humidity.

The caveat that matters most

A DX coil or a chilled water coil cools the air and, if the coil is cold enough, removes moisture. An air washer cools the air and adds moisture. Where the supply air must be dry, because the process, the product or the equipment cannot tolerate humidity, the washer is not an alternative to refrigeration, and a kilowatt-hour comparison is irrelevant. Where the supply can be humid, as for general ventilation of a factory in a dry climate, the washer wins on energy by a wide margin.

How much moisture is added is quantified in the next article, and how much cooling is possible at all is the subject of wet-bulb depression.

A sense check on the numbers

Two checks are worth doing on any such comparison. First, convert the washer’s fan and pump power back into a percentage of the cooling it delivers: in the dry cases it is only two to three percent, which is why the technology is so cheap to run, and in the humid case it climbs toward eight percent. Second, ask what the refrigerated alternative would deliver beyond sensible cooling. A coil that is cold enough also removes moisture, and that dehumidification has value in a humid climate that the washer cannot provide. When a vendor quotes a single headline saving without stating the weather and the supply humidity, the number is not comparable with anything else.

What the model leaves out

  • Water. The washer uses water and the refrigeration plant, if water-cooled, does too. The washer’s consumption is calculated in this article.
  • Capital cost. A washer is usually cheaper to buy than a refrigerated system of the same sensible capacity.
  • Hybrid use. Many plants use the washer as a pre-cooler ahead of a coil, which lets the chiller be smaller and run at a better COP.
  • Maintenance and water treatment, which are real costs of the washer.
  • Part load. Refrigeration COP changes with load. The washer’s fan and pump power are nearly constant, so at low load its relative advantage falls.

The right comparison is annual, with real weather data for the site and a real COP curve, and it is worth doing for a large installation. Hourly weather files are available for most cities, and a spreadsheet that applies the washer’s efficiency and the plant’s COP hour by hour is an afternoon’s work.

Where this fits with NextAir

NextAir can model your site with hourly weather data and compare a washer, a pre-cooler arrangement and refrigeration for your airflow. Send the design conditions and the required supply to our industrial air washer manufacturer team. Our air washer guide sets out where each technology fits, and the warehousing and printing and packaging pages show typical duties.

Sources

  1. Plant Engineering (US DOE Motor System BestPractices material). Building energy efficiency into fan systems.
  2. NOAA. Fast Facts: highest dew points and heat index.

Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.

Frequently Asked Questions

Is an air washer cheaper to run than air conditioning?

In dry, hot weather, usually much cheaper per kilowatt of sensible cooling, because it uses only a fan and a pump. In humid weather its cooling falls and the advantage shrinks.

Why does the air washer's advantage depend on the weather?

Its cooling is limited by the wet-bulb depression, while its fan and pump power stay roughly constant, so the cooling per kilowatt of electricity rises and falls with the weather.

Can I compare an air washer with DX on energy alone?

Only if the supply humidity does not matter. Refrigeration dehumidifies and an air washer adds moisture, so they deliver different air.

What COP should I assume for DX and chilled water?

Use the figures for your equipment at the actual load and ambient temperature. The 3 and 5 here are round-number assumptions for illustration.

Does an air washer use more water than other options?

Yes, it evaporates water by design, while air-cooled DX uses none. In water-scarce regions that cost belongs in the comparison.