How Much Moisture Does an Air Washer Add? Kilograms per Hour per 1,000 m³/h
By the NextAir Systems engineering team. Last reviewed October 2026.
Cooling by evaporation is a swap: the air loses sensible heat and gains water vapor. The temperature falls and the dew point rises. For comfort ventilation in dry air that is exactly what you want. For a textile hall with a humidity target, a printing room, or a space with metal and electronics, it can be the thing that breaks the specification.
This guide quantifies the moisture added, expresses it per 1,000 m³/h so you can scale it, and checks the resulting dew point against a real limit.
The short version
- At 85% efficiency and 42 °C, 20% RH, a washer adds about 6.4 g of water to each kilogram of air, which is 7.0 kg/h per 1,000 m³/h, and raises the dew point from 14.4 to 22.0 °C.
- The supply is cooler but much wetter in absolute terms, with RH commonly 75 to 95%.
- ASHRAE’s recommended envelope for data equipment caps the inlet dew point at 15 °C. None of the four conditions here gives a washer supply below 22 °C, so a washer alone cannot meet it.[1]
- Where the dew point matters, use the washer as a pre-cooler ahead of a coil, or choose refrigeration.
Moisture added
Adiabatic evaporative cooling follows a line of constant wet-bulb temperature on the psychrometric chart. As the dry-bulb falls the humidity ratio rises, by an amount fixed by the entering condition and the saturation efficiency. The mass of water added per hour is the dry air flow times that rise.
| Entering condition | Entering dew point (°C) | Supply temperature (°C) | Supply RH (%) | Supply dew point (°C) | Moisture added (g/kg) | Water added (kg/h per 1,000 m³/h) |
|---|---|---|---|---|---|---|
| Hot, dry inland (scenario) | 14.4 | 26.1 | 78 | 22.0 | 6.4 | 7.0 |
| Hot, moderately dry (scenario) | 19.1 | 27.3 | 83 | 24.1 | 5.1 | 5.6 |
| Hot, mixed (scenario) | 25.8 | 30.0 | 90 | 28.1 | 3.3 | 3.6 |
| Hot humid coastal (scenario) | 28.7 | 30.8 | 94 | 29.8 | 1.7 | 1.9 |
The water added falls as the weather gets wetter, from 7.0 kg/h per 1,000 m³/h in the dry case to 1.9 kg/h in the humid one, because there is less depression to work with. But the supply dew point rises in every case, to between 22.0 and 29.8 °C. That is the number to compare with your requirement. The figures assume 85% efficiency and are for illustration.
Worked example. A printing hall of 40,000 m³/h of supply air at the 42 °C, 20% RH condition receives 280 kg of water an hour from the washer, or about 6,720 litres a day, all of which ends up in the hall’s air and has to leave through ventilation or leakage. If the room is held at a stable humidity by ventilation alone, the room’s RH will sit near that of the supply, around 78%, which is far above the 50 to 55% many presses prefer.
Checking against a real limit
ASHRAE’s guidelines for data processing environments recommend a dew point range of −9 to 15 °C at the equipment inlet, with a 60% RH maximum, and allow up to 17 °C for class A1 and 24 °C for class A4.[1] Against those, every washer-only supply in the table is above the recommended ceiling and above the class A1 allowable. Only the driest case, at about 22 °C, falls inside the 24 °C allowable of class A4 equipment, and only just. The practical consequence is that data halls in hot climates use evaporative cooling indirectly, so the moist air never reaches the equipment, or combine it with a coil.
Ways to keep the benefit and cut the moisture
- Indirect evaporative cooling. The wet air is on one side of a heat exchanger and the supply air on the other. The supply is cooled with no added moisture.
- Pre-cooler ahead of a coil. The washer takes the first part of the cooling cheaply, and the coil finishes the job and dries the air, with a smaller load, as in the comparison in the energy article.
- Seasonal operation. Run the washer when the dew point is low enough and bypass it otherwise.
- Humidity control on the room. A dehumidifier can pull the humidity back down, though it uses energy to undo what the washer added, as in the moisture load calculation.
- Choose the efficiency to suit. A lower efficiency adds less moisture, with a smaller temperature drop, as the table in the saturation efficiency article shows.
How to use the table
- Take your design dry-bulb and wet-bulb, or RH, and find the nearest row.
- Multiply the water added per 1,000 m³/h by your airflow in thousands to get kilograms an hour.
- Compare the supply dew point with the dew point your process or equipment needs.
- If the supply is too wet, decide between an indirect system, a coil, or a lower efficiency.
- If you must remove the moisture afterwards, size that equipment on the water added, using the method in the moisture load guide.
Where the moisture is welcome
Not every application minds. Textile spinning and weaving rooms actually need humid air, because fibres run better with moisture, and an air washer both cools and humidifies them in a single step. Food and agricultural spaces, greenhouses and some warehouses also benefit. The question is always whether the added water is a cost or a feature. Decide which before you choose the equipment.
Where this fits with NextAir
Send our industrial air washer manufacturer team your target supply temperature and humidity, and we will say whether a washer alone, a washer with a coil, or refrigeration is the right choice. Our air washer guide covers the technology, and the textile page covers the sector where added humidity is most often a benefit.
Sources
- ASHRAE TC 9.9. Thermal Guidelines for Data Processing Environments, 4th ed., Table 2.1 (2015 guidelines, SI).
- NOAA. Fast Facts: highest dew points and heat index.
Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.
Frequently Asked Questions
Does an air washer add humidity?
Yes. It cools by evaporating water into the air, so the supply air is cooler but carries more moisture, with a higher dew point and RH.
How much water does an air washer add to the air?
At 85% efficiency, between about 1.9 and 7.0 kg/h per 1,000 m³/h across the conditions in the table, more in dry weather.
Can I use an air washer where humidity is controlled?
Only with care. A washer alone raises the supply dew point, so an indirect arrangement, a pre-cooler with a coil, or refrigeration is usually needed where the humidity is a requirement.
What is the supply RH of an air washer?
Typically 75 to 95%, depending on the entering condition and the efficiency.
Is the added humidity ever useful?
Yes. Textile mills, greenhouses and some agricultural and food spaces want humid air, and a washer supplies both cooling and humidity.