Cleanroom Air Filtration System Supplier: From Air Changes to Airflow to Unit Size

NextAir Systems, Faridabad, India. Last reviewed October 2026.

A cleanroom is specified by what is allowed to be in the air, and delivered by how much clean air goes through it. The link between the two is the air change rate, and the number a client gives you is often not the number the supply unit has to deliver, because the supply may be fresh air, recirculated air or a mixture, and the filters sit in more than one place.

NextAir’s NAP central air purification units offer HEPA filtration for cleanroom, healthcare or biological-containment duties. This page shows how to turn a room into an airflow, what part of a cleanroom system a unit like ours is, and what to ask a supplier before you commit.

At a glance

  • NAP units supply continuous treated fresh air from 500 to 20,000 CMH, with HEPA (99.97% at 0.3 microns) available as an upgrade to, or in addition to, the fine filter.
  • A 300 m³ room (100 m² at 3 m) at 20 air changes an hour needs 6,000 m³/h, which is NAP-7500; at 60 changes an hour it needs 18,000 m³/h.
  • The air change rate and the cleanliness class come from your standard, your client or your regulator. The numbers below are illustrations, not requirements.
  • The most overlooked part is the final filter’s seal and the installed leak test.

Start with the room and the standard

The cleanliness class sets the allowable particle count, and the standard or client specification sets the air change rate, the pressure cascade, the temperature and humidity. A supplier should ask you for the standard before quoting, and not suggest a rate. We do not publish a required air change rate here, because it depends on the class and the activity, and a rule of thumb copied into a project is how clean rooms fail validation.

From air changes to airflow

Airflow is room volume times air changes per hour. The table uses a 100 m² room with a 3 m ceiling at four illustrative rates, and shows the NAP model that would cover the airflow if the whole supply came from one unit. In practice a cleanroom often has terminal HEPA filters in the ceiling and a recirculation loop, and a central unit supplies the fresh air and the first stages.

Air changes per hour (illustrative)Airflow (m³/h)NAP model covering it as a single unit
103,000NAP-3500
206,000NAP-7500
4012,000NAP-12500
6018,000NAP-20000

At 60 changes an hour the supply for even a small room is more than 18,000 m³/h, which shows why high-class rooms use recirculation and not 100% fresh air. Ask the designer where the airflow comes from, so you know whether the central unit has to deliver the whole figure or only the fresh-air portion.

Do not forget the humidity side. Many cleanroom processes need a controlled humidity as well as controlled particles, and the central unit alone does not dehumidify. Where the humidity target is low, a desiccant dehumidifier or an air handling unit with a dedicated stage works alongside the filtration, and the two should be designed together so that the airflow, the pressure drop and the control strategy do not fight each other.

What a central unit does in a cleanroom system

  • Treats fresh air with a MERV 8 pre-filter, a MERV 13-14 fine filter, UV-C and, if required, HEPA, so the downstream HEPA filters are protected and last longer.
  • Carries the positive-pressure supply that keeps the room above its surroundings.
  • Adds optional gas-phase treatment where odour or VOC in the outside air matters.
  • Is not a substitute for terminal HEPA filtration in a classified space. Those filters, their housings and the leak test belong to the room design.

Filter ratings and leaks

HEPA at 99.97% at 0.3 microns is the US-style definition, and EN 1822 grades filters at the most penetrating particle size, H13 at least 99.95% and H14 at least 99.995%.[1] The class on a datasheet says nothing about the installation. A bypass of 0.1% of the air around a filter can limit overall efficiency to about 99.9% whatever the media, so an installed leak test and a sealed housing are part of the specification, as how to read a HEPA datasheet explains.

Pressure drop and energy

HEPA stages add resistance, and the fan runs continuously. Compare quotations on pressure drop at clean and final condition, and on face velocity. The relationship between area, resistance and energy is in filter face area, velocity and energy, and the economics of when to change a filter are in filter change-out economics.

Questions to ask a cleanroom filtration supplier

  1. Which standard and class are the filters tested to, and where is the report?
  2. How is each filter leak-tested before delivery, and what installed test do you recommend?
  3. What is the clean and final pressure drop at design airflow?
  4. How does the unit cope with humidity and temperature control, or does it leave that to the air handling unit?
  5. What access does each stage have for filter change without breaking the seal of the others?
  6. How does the unit scale if the room’s airflow grows?

For the humidity and temperature side of a cleanroom, see our cleanroom air handling units and dehumidifiers, and for a checklist of supplier questions, how to choose an air purification system manufacturer.

What to send us for a quotation

  • The cleanliness class and the standard it comes from
  • Room volume and the air change rate required, and whether supply is fresh or recirculated
  • The pressure cascade and the temperature and humidity requirements
  • HEPA class and leak-test requirement
  • Outdoor air quality and any gas-phase needs
  • Electrical supply, space and validation requirements

Send these to us through our contact page and we will say what part of your system the NAP unit can cover and with what stages. See the NAP range, our guide to centralized air purification, and the pharmaceutical and healthcare pages.

Sources

  1. Camfil. Comparison chart: ASHRAE 52.2, ISO 16890, EN 779, EN 1822.

Frequently Asked Questions

Do you supply cleanroom air filtration?

Our NAP units offer HEPA filtration for cleanroom, healthcare or biological-containment duties, as part of the treatment of the air supplied to the space. The room's terminal filtration and validation belong to the cleanroom design.

What air change rate does a cleanroom need?

It depends on the cleanliness class and the activity, and comes from your standard or client. We do not give a rule of thumb.

Is your unit a replacement for ceiling HEPA filters?

No. It treats the supplied air and protects downstream filters. Terminal HEPA filters in a classified room are part of the room design.

Why does the leak test matter?

Because a small bypass can limit overall efficiency to well below the class of the media.

What airflow range do your units cover?

500 to 20,000 CMH in a single unit, with banks or a sectionalised casing above that.

Talk to Our Engineering Team

Call +91-9311805618 or use our contact form for a facility-specific recommendation.

Contact Us