Landfill and Waste Plant Odor Control Supplier: Transfer Stations, Tipping Halls and Composting

NextAir Systems, Faridabad, India. Last reviewed October 2026.

Waste is the odor source with the longest list of complaints, because it is large, it is outdoors or half-indoors, and it changes by the hour. A landfill, a transfer station or a composting site rarely has a single stack to treat. It has a building, a tipping floor or a windrow, and the first decision is not which unit to buy but how much air you are going to try to treat.

NextAir builds dry odor control adsorbers for waste management and landfills, covering landfills, transfer stations and composting, in horizontal units to 20,000 CMH, multi-bank systems and vertical vessels. This page is about turning a building into an airflow, and an airflow into a sensible equipment choice.

At a glance

  • Treating a whole reception building is expensive: at 4 air changes an hour, a 60 x 30 x 10 m tipping hall needs 72,000 m³/h, which is vessel or bank territory.
  • Capturing the tipping area, with a hood, an air curtain or an enclosure, can cut that by an order of magnitude.
  • Our single horizontal units go to 20,000 CMH, multi-bank systems above that, and vertical vessels of 25,000 to 80,000 CMH for large-scale facilities.
  • Odor emission rate is concentration times flow, and EN 13725 defines the odour unit by dilution to the detection threshold.[1]

The building is the airflow

A reception building holds odor in its air until the ventilation removes it. The volume of air to treat is the building volume times the air change rate, and the air change rate is a choice: a design standard, a regulator or your own judgement sets it. The table uses illustrative buildings and illustrative air change rates, which are assumptions and not requirements, to show how quickly the airflow grows.

BuildingVolume (m³)Air changes per hour (assumed)Airflow to treat (m³/h)Equipment class
Small transfer station4,800419,200single horizontal unit
Tipping hall18,000472,000vertical vessel or bank
Composting reception hall11,250667,500vertical vessel or bank
Large waste reception building38,4003115,200bank of vessels

A small transfer station fits in a handful of our largest single units or a vessel. A large waste reception building needs a very large vessel or several. This is the arithmetic that turns an odor project into a capital project, and it is why the first question to ask is whether you can treat less air, as set out in capture at the source.

Treat the source, not the room

  • Hood or enclose the tipping point. Extracting at the point where waste is dropped captures most of the odor at a small fraction of the airflow.
  • Air curtains and fast doors keep the building at slightly negative pressure so odor does not leak when vehicles come and go.
  • Cover and cap. Waste bunkers, leachate tanks and sumps can be covered and vented to the unit.
  • Keep the rest of the building ventilated for people, with clean air, because it no longer carries the odor.

The compromise is cost against complaints. A site next to housing may need the building treated. A site in open country may need only the tipping point. Our guide to the arithmetic of odour dilution shows why trying to dilute the odor in the air is rarely cheaper.

From odour concentration to emission rate

An olfactometry result gives odour concentration in ouE/m³, defined so that 1 ouE/m³ is the concentration at the detection threshold.[1] Multiply by the airflow to get the emission rate. For a 40,000 m³/h exhaust at 500 ouE/m³, the emission is 500 × 40,000 ÷ 3,600 = 5,556 ouE/s. How an odor survey is read is in odour units and EN 13725. The standard covers emissions from stationary sources, not the odor a neighbour experiences, so a survey describes the source and a complaint record describes the receptor.

Why waste streams are hard on equipment

Waste air varies with the weather, the delivery schedule and the age of the material, so the load on the media is uneven. Composting exhaust is often warm and humid, and a stream with a lot of dust needs the pre-filter looked after: a MERV 8 pre-filter sits ahead of every unit’s bed to keep dust off the media. Ask the supplier how the media performs at your humidity, how often the pre-filter should be changed and what a stoppage does to the bed. Our standard fit includes a local panel that shows the pressure drop across the bed and run hours, and continuous outlet gas monitoring is an option.

Sizing and options

Single horizontal units run from 1,000 to 20,000 CMH. Above that, a multi-bank system of two or more units suits sites with several odor sources or where units must be serviced one at a time, and vertical vessels with a radial-flow annular bed serve large capacities up to 80,000 CMH. Where odor control cannot be interrupted, two vessels, each sized for the full flow, are the usual arrangement. Options include beds in series for mixed odorants, a stainless steel housing for corrosive or coastal sites and a variable frequency drive. The media life calculation is in how to estimate media life.

To compare suppliers use how to choose an odor control adsorber manufacturer, and for sewage-side sites see our pump station odor control units.

What to send us for a quotation

  • Building dimensions and the odor sources inside it, or the airflow if known
  • Odour survey results or gas readings, with any hydrogen sulfide and ammonia
  • Exhaust temperature and humidity, and the dust loading
  • Operating pattern: continuous, or only during deliveries
  • The odor target and any complaint history
  • Site electrical supply, space, and whether the site is coastal or corrosive

Send these to us through our contact page and we will tell you whether to treat the source or the building, and size the unit or the vessel. See the odor control adsorber range, our dry odor control adsorber guide and the waste management and landfills page. A fan for the extraction is usually a centrifugal blower.

Sources

  1. CEN (EN 13725:2022), via EVS. EN 13725:2022 Stationary source emissions: determination of odour concentration by dynamic olfactometry and odour emission rate.

Frequently Asked Questions

What odor control do you supply for landfills and transfer stations?

Dry odor control adsorbers: horizontal single units from 1,000 to 20,000 CMH, multi-bank systems above that, and vertical vessels for 25,000 to 80,000 CMH.

Should I treat the whole building or the source?

Where complaints allow, treat the source: a hood or enclosure at the tipping point cuts the airflow dramatically. A site next to housing may still need the building treated.

How do I size odor control for a reception building?

Building volume times the air change rate gives the airflow. The rate is set by your standard or regulator, and capturing only the source reduces it.

Can the unit cope with humid composting exhaust?

Ask the supplier how the media performs at your humidity. A MERV 8 pre-filter is standard to keep dust off the media, and outlet gas monitoring is an option.

Can two units provide redundancy?

Yes. Where treatment cannot be interrupted, two vessels each sized for the full flow are the usual arrangement.