Sewage and Pump Station Odor Control Unit Manufacturer: Compact Dry Units for Unattended Sites

NextAir Systems, Faridabad, India. Last reviewed October 2026.

A sewage pump station is the odor source nobody sees. It sits in a residential street, it is unmanned, it releases hydrogen sulfide in bursts when the wells fill and empty, and the people who live nearby know exactly where it is. The equipment that treats it has to be small, quiet, dependable and cheap to visit.

NextAir manufactures dry odor control units for pumping stations and lift stations, starting with a compact box at 1,000 CMH, and larger multi-cell units for headworks and bigger wells. This page explains how to size one from the wet well, and what a site like this demands.

At a glance

  • Our smallest units suit a small pumping station or lift station at 1,000 CMH, and 2,000 CMH covers a pumping station or a small headworks, both in compact boxes.
  • A wet well’s airflow comes from its headspace and your ventilation standard. At an assumed 6 air changes an hour, a 100 m³ headspace needs 600 m³/h.
  • OSHA has a policy classifying a wet well as a Class 1, Division 1 location, so the electrical equipment and entry procedures need to suit it.[1]
  • Capturing only the wet well’s airspace, not the whole building, keeps the unit small.

What a pump station demands of its odor unit

  • Unattended running. No operator is there to notice a problem, so the unit needs a local panel that shows pressure drop across the bed and run hours, and ideally an outlet gas sensor. Continuous outlet gas monitoring is an option on our units.
  • Visits are expensive. A crew drives out, so media life matters more than for a plant with staff. See how to estimate media life.
  • Neighbours. Noise and appearance matter in a street. A direct-drive backward-curved centrifugal fan is quiet for its duty, but check the sound level at the boundary using sound power to sound at the fence.
  • Corrosion. A stainless steel housing is an option where the air is corrosive or the site is coastal, and standard units are mild steel with a powder-coat finish.
  • Power. Many stations have a small supply. A variable frequency drive on the fan is available for part-load savings.

Sizing from the wet well

The air to treat is the wet well’s headspace times the ventilation rate your design standard sets. We use 6 air changes an hour to show the arithmetic, which is an assumption and not a requirement. The table converts headspace to airflow and to a unit within our range.

Headspace (m³)Airflow at 6 changes an hour (m³/h)Unit within our range
201201,000 CMH compact box
503001,000 CMH compact box
1006001,000 CMH compact box
2001,2002,000 CMH compact box
4002,400multi-cell unit, up to 20,000 CMH
8004,800multi-cell unit, up to 20,000 CMH

The 20 m³ and 50 m³ wells need less than our smallest unit’s 1,000 CMH rating, which means the unit would run below its rating and give a longer contact time, while a 400 m³ well needs a multi-cell unit. A worked example from wet well to fan power and running cost is in sizing a compact adsorber for a pump station.

The hazardous-area question

A wet well can hold hydrogen sulfide and flammable gas, and OSHA has issued a policy on classifying a wet well as a Class 1, Division 1 location.[1] That affects the fan motor and any instruments in or near the well. Whether a fan or instrument can sit in or near a classified zone is a design question for your site, so state the classification in the enquiry, because it can change the layout and where the unit stands.

Staying small: capture the airspace

The best way to keep the unit small is to treat only the air that needs treating, which means covering the source and extracting its headspace instead of ventilating a room. The comparison is in capture at the source.

A routine for an unattended site

  1. At each visit, read the pressure drop across the bed and the run hours from the local panel, and write them down.
  2. Compare the pressure drop with the last visit. A steady rise suggests dust on the pre-filter; a fall suggests channelling or a leak.
  3. Check the outlet gas reading if a sensor is fitted, and test it with a known gas on a set interval.
  4. Change the pre-filter on its interval, and the media on the interval worked out from the sulfide load.
  5. Record the media change date and the spent media’s destination.

Across a network, a single standard unit and one spares list make this routine the same at every site, and turn a media change into a half-day task for any crew.

Think about access too. A media change needs vehicle access to the unit, room to open the panels, and a safe way to lift spent media clear. A unit squeezed against a boundary wall with no working room turns every visit into a problem, so agree the clear space around it at the design stage and not at the first change-out.

Choosing a supplier

For a network of stations, ask for a standard unit you can repeat, a spares list common to all sites, and a clear media change-out routine, so the crew can do it without calling the factory. Our buyer’s guide lists the checks, and the limits that apply to people on site are in hydrogen sulfide limits.

What to send us for a quotation

  • Wet well dimensions, headspace and the ventilation rate your standard requires
  • H₂S readings over several days, including peaks, and any other odorants
  • Site climate, whether coastal, and the electrical supply available
  • Noise limit at the nearest dwelling and any planning constraints on appearance
  • The hazardous-area classification of the well and the surrounding area
  • Number of stations, and whether a standard repeat design is wanted

Send these to us through our contact page and we will recommend a compact unit and the media interval for your site. See the odor control adsorber range, our dry odor control adsorber guide and the wastewater treatment page. For the whole network, the dry odor removal units guide explains the same product by its other name.

Sources

  1. US OSHA. Hydrogen Sulfide: Standards.

Types and variants we build

Frequently Asked Questions

What odor control units do you make for sewage pump stations?

Dry odor control adsorbers starting with a 1,000 CMH compact box for a small pumping or lift station, and 2,000 CMH for a pumping station or small headworks, with multi-cell units above that.

How do I size a unit for a wet well?

Multiply the headspace volume by the ventilation rate your standard sets, for the airflow, then check media life from the sulfide load.

Do you offer stainless steel housings?

Yes, as an option where the air is corrosive or the site is coastal. Standard housings are mild steel with a powder-coat finish.

Can the unit detect when the media is spent?

Continuous outlet gas monitoring is an option, so breakthrough is detected as it happens.

Is a wet well a hazardous area?

OSHA has a policy classifying a wet well as a Class 1, Division 1 location, so equipment and entry procedures need to suit it. Raise the classification in your enquiry.