Saturation Efficiency Explained: What Supply Temperature Can You Really Expect?
By the NextAir Systems engineering team. Last reviewed October 2026.
Every air washer datasheet carries a figure called saturation efficiency, and it is the figure that tells you the supply temperature. It is also the figure most easily misread, because it is a percentage of something that changes with the weather, not a fixed temperature drop.
Here is the definition, a worked table for one set of weather conditions, and what the number depends on in the machine itself.
The short version
- Saturation efficiency = (entering dry-bulb − leaving dry-bulb) ÷ (entering dry-bulb − entering wet-bulb). It is the share of the wet-bulb depression the washer achieves.
- At 40 °C and 20% RH the wet-bulb is 22.0 °C, a depression of 18.0 K. A 90% efficient washer delivers 23.8 °C, and a 70% one 27.4 °C.
- The extra efficiency costs more water contact: longer chambers, more spray banks or more media. Each step adds pressure drop and cost.
- Efficiency is quoted at one airflow and one water condition, so ask what it is at yours.
The definition
If the air entering an air washer is at a dry-bulb temperature T₁ with a wet-bulb of T_wb, and leaves at T₂, the saturation efficiency is (T₁ − T₂) ÷ (T₁ − T_wb). A 100% efficient washer would saturate the air and deliver it at the wet-bulb temperature. Real washers do not, because the air does not fully equilibrate with the water in the time it spends in the chamber.
The consequence is that the cooling you get is a share of whatever the weather offers. A given washer delivers more kelvin of cooling on a dry day than on a humid one, as the table in the wet-bulb depression article shows for 85%.
A worked table
We take 10,000 m³/h of air at 40 °C and 20% RH, with a wet-bulb of 22.0 °C and a humidity ratio of 9.2 g/kg, and vary only the efficiency.
| Saturation efficiency | Supply air (°C) | Cooling (K) | Gap to wet-bulb (K) | Supply RH (%) | Moisture added (g/kg) | Sensible cooling (kW) |
|---|---|---|---|---|---|---|
| 60% | 29.2 | 10.8 | 7.2 | 53 | 4.3 | 34 |
| 70% | 27.4 | 12.6 | 5.4 | 62 | 5.0 | 40 |
| 80% | 25.6 | 14.4 | 3.6 | 72 | 5.8 | 45 |
| 90% | 23.8 | 16.2 | 1.8 | 84 | 6.5 | 51 |
| 95% | 22.9 | 17.1 | 0.9 | 91 | 6.9 | 54 |
Worked example. Moving from 70% to 90% efficiency lowers the supply from 27.4 to 23.8 °C, an extra 3.6 K of cooling, and adds 1.5 g/kg of moisture. The sensible cooling rises from 40 to 51 kW. The supply RH climbs from 62% to 84%. A buyer who sees only the temperature misses that the room humidity rises with it.
Notice also the gap-to-wet-bulb column. Each ten points of efficiency removes less absolute temperature as you approach the top: the last 10 points between 80% and 90% are worth only about two kelvin here, but they take a longer chamber and a higher air pressure drop to achieve. Treat the high end of the efficiency range as a premium you pay only when the process truly requires it.
Working backwards from a supply target
Most projects start from the supply temperature they need, not the efficiency. Rearranging the definition gives the efficiency required: (T₁ − target) ÷ (T₁ − T_wb). For air at 42 °C and 20% RH, with a wet-bulb of 23.3 °C:
| Target supply temperature (°C) | Efficiency required (%) | Verdict |
|---|---|---|
| 24 | 96 | Not realistic for one stage |
| 26 | 86 | Demanding |
| 28 | 75 | Readily achievable |
| 30 | 64 | Readily achievable |
The table shows why a target close to the wet-bulb is expensive. Asking for 26 °C from 42 °C and 20% RH needs more than 80% efficiency, which is achievable. Asking for 24 °C needs more than 95%, and the last few percent cost far more than the first sixty. If the process can live with 28 °C, a much simpler washer will do. Agree the required temperature before you agree the efficiency.
What sets efficiency in the machine
- Contact time. A longer chamber or a lower air velocity gives the air more time with the water.
- Water surface area. More spray banks, finer droplets or deeper wetted media expose more area.
- Water distribution. Even spray and no dry spots matter. A bank with blocked nozzles gives lower efficiency than its datasheet.
- Eliminators. These remove carried droplets and add pressure drop.
- Water temperature. The water in the sump rises toward the wet-bulb temperature, so it does not need chilling. If it is much warmer or colder, performance changes.
Greater efficiency comes with higher fan pressure drop and higher pump power. The marginal gain falls as you approach the top of the range, so the difference between 90% and 95% usually costs more than between 70% and 80%. Choose the efficiency the process needs and not the highest on offer.
Reading a datasheet
- Find the entering condition at which efficiency is stated. It is usually a dry-bulb and wet-bulb pair.
- Find the airflow, because efficiency falls as air velocity rises.
- Ask whether the figure is for the full unit including eliminators, or for the media alone.
- Ask for the pressure drop on the air side, and the pump flow and head on the water side.
- Ask for the leaving wet-bulb or dew point, so you can check the humidity you will get, as in how much moisture an air washer adds.
If the water side is poorly managed, the performance falls and the risks rise, which is why water treatment and bleed-off belongs in the same conversation as efficiency.
Where this fits with NextAir
Our air washers are sized for the saturation efficiency your process needs, up to 50,000 CFM per unit, with multi-bank designs for tighter approaches. Tell our industrial air washer manufacturer team the entering condition and the supply you need, and we will state the efficiency, pressure drop and water flow at that point. Read our air washer guide for the technology, and see textile and metalworking for typical duties.
Sources
- NOAA. Fast Facts: highest dew points and heat index.
- Guinness World Records. Highest dewpoint temperature.
Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.
Frequently Asked Questions
What is saturation efficiency?
The share of the wet-bulb depression that an air washer achieves: (entering dry-bulb minus leaving dry-bulb) divided by (entering dry-bulb minus entering wet-bulb).
What saturation efficiency is typical for an air washer?
That depends on the design. Efficiencies from about 60% to above 90% are seen, with higher values needing longer contact time and more water surface.
Does higher efficiency mean higher humidity?
Yes. More cooling by evaporation means more water vapor added, so the supply air's RH rises as the temperature falls.
Can an air washer reach 100% efficiency?
No. That would require the air to fully saturate, which real equipment does not achieve in the time available.
Why does the datasheet efficiency not match my site?
It is stated at a particular entering condition and airflow. At different conditions or higher velocities, efficiency changes.