What WHO’s 2021 Particle Guidelines Mean for a Building’s Air System

By the NextAir Systems engineering team. Last reviewed October 2026.

In September 2021 the World Health Organization halved its annual guideline for fine particles, the first major revision in 15 years. The headline was about cities and policy. For anyone running a building, the practical question is narrower: if the air outside exceeds the guideline, how good does the filtration inside have to be?

That can be answered with one line of arithmetic, and the answer is sobering for sites with heavy outdoor pollution. Here are the numbers, the calculation, and what it implies for filter staging.

The short version

  • WHO’s 2021 guidelines for PM2.5 are 5 µg/m³ as an annual mean and 15 µg/m³ as a 24-hour mean. For PM10 they are 15 and 45 µg/m³.[1]
  • In 2019 more than 90% of the world’s population lived in areas where concentrations exceeded the older 2005 PM2.5 guideline of 10 µg/m³.[1]
  • To bring 100 µg/m³ outdoors down to the 15 µg/m³ 24-hour guideline inside, the whole system must remove 85% of PM2.5. To reach the annual 5 µg/m³ it must remove 95%.
  • One filter bank rarely does that alone. Staged filtration, a tight envelope and attention to bypass are what close the gap.

What WHO changed

WHO released revised air quality guidelines on 22 September 2021, tightening almost all of the levels.[2] The values for particles are shown below, with the 2005 numbers for comparison.[1]

PollutantAveraging time2005 guideline (µg/m³)2021 guideline (µg/m³)
PM2.5Annual105
PM2.524-hour2515
PM10Annual2015
PM1024-hour5045

These are guidelines for the air people breathe, with health evidence behind them. They are not laws, and national standards are usually looser. India’s national ambient limit for PM10, for example, is reported as 60 µg/m³, four times the WHO annual guideline.[2] But they are the benchmark that hospitals, schools and multinational tenants increasingly ask about, and they set the target for a building that wants to say it protects its occupants.

The one-line calculation

If the outdoor concentration is C and you want the indoor concentration to be T, the system must remove a fraction 1 − T ÷ C of the particles. This is the overall efficiency of everything between the outside air and the occupant: the filters, the leakage paths and the indoor sources. Here is the requirement for the two PM2.5 guideline levels.

Outdoor PM2.5Efficiency needed for 15 µg/m³ (24-hour)Efficiency needed for 5 µg/m³ (annual)
25 µg/m³40%80%
50 µg/m³70%90%
100 µg/m³85%95%
200 µg/m³92%98%

Worked example. A building in a polluted city sees 100 µg/m³ of PM2.5 on a bad day. To hold 15 µg/m³ indoors, the system must remove 85% overall. A single ePM1 70% filter on the outdoor air does not deliver that, and neither does a leaky envelope. Put a prefilter and an ePM1 stage in series, seal the building, and the overall figure gets within reach. To hold 5 µg/m³ needs 95%, and that is a high-efficiency final stage, in the territory of the classes in MERV, ISO 16890 and EN 1822.

Why one filter is not enough

  • Filters have a size curve. A rating is for a size range. A filter reported as ePM1 65% captures about two-thirds of particles between 0.3 and 1 µm, which is not the same as two-thirds of PM2.5 mass.
  • Air bypasses. Through leaks around frames, doors and the building envelope, air takes the easy route. A tight envelope matters as much as the filter class.
  • Indoor sources add to the total. Cooking, printing, people and cleaning add particles that the outdoor-air filter never sees. Recirculation through a filter handles those.
  • Efficiency falls in service. ISO 16890 reports conditioned efficiency because it can drop with loading or charge loss.[3]
  • Averaging matters. Meeting a 24-hour guideline on the worst day is a harder test than meeting an annual one on the average day.

What it means for system design

A system aiming at the WHO guidelines in a polluted city typically has three parts. A coarse prefilter takes the large dust and protects what follows. A fine filter, ePM1 or at least ePM2.5, does the main work on the outdoor air. A recirculating high-efficiency stage cleans the indoor air continuously. Pressure drop and energy rise with each, so the arrangement should be designed to keep face velocity low, as shown in the face area article.

The mass of dust you can expect to collect, and so the maintenance cost, is estimated in the dust load calculation. If you are setting a target for a specific facility, measure first: a few months of outdoor PM data and a few weeks inside will tell you what you are actually trying to achieve.

Gases are a separate question

WHO’s guidelines also cover NO₂, ozone, SO₂ and CO, and none of them is addressed by a particle filter. Where outdoor gas pollutants matter, as near heavy traffic or industry, a gas-phase stage is needed, which is a different technology from particle filtration. Mention it in the brief at the start, so the design includes the space and pressure drop for it.

Where this fits with NextAir

NextAir designs centralized air purification systems in staged cartridges, from prefilters through ePM1 and HEPA stages, with optional gas-phase and UV-C modules. Send the outdoor PM data and the indoor target to our air purification system manufacturer team and we will propose a staging and its pressure drop. For the system overview, read our guide to centralized air purification, and see commercial buildings for a typical application.

Sources

  1. DieselNet (summary of WHO release, 23 Sept 2021). WHO releases new Global Air Quality Guidelines.
  2. IQAir. New WHO air quality guidelines will save lives.
  3. Camfil. Comparison chart: ASHRAE 52.2, ISO 16890, EN 779, EN 1822.

Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.

Frequently Asked Questions

What are the WHO 2021 PM2.5 guidelines?

5 µg/m³ as an annual mean and 15 µg/m³ as a 24-hour mean, down from 10 and 25 µg/m³ in 2005.

What are the WHO 2021 PM10 guidelines?

15 µg/m³ as an annual mean and 45 µg/m³ as a 24-hour mean.

How efficient must a building's filtration be to meet them?

Divide the target by the outdoor concentration and subtract from one. At 100 µg/m³ outdoors, meeting 15 µg/m³ needs 85% overall PM2.5 removal and meeting 5 µg/m³ needs 95%.

Is the WHO guideline a legal limit?

No. It is a health-based guideline. National standards differ and are generally less strict.

Do particle filters remove gaseous pollutants?

No. Gases such as NO₂, ozone and SO₂ need a gas-phase stage. Particle filters address particulate matter only.