AHU Fan Power: Static Pressure, Specific Fan Power and What a Pascal Costs
By the NextAir Systems engineering team. Last reviewed October 2026.
The fan is usually the largest electricity user in an air handling unit, and fan power is set by two things: how much air it moves and how much pressure it has to push against. Airflow comes from the brief. Pressure is the sum of everything the air passes through, and it is where most of the avoidable energy is lost.
This guide builds a pressure budget for a typical unit, converts it to power and annual cost, and shows how much a few small design changes save. The numbers are illustrative, and the method is the useful part.
The short version
- A 20,000 m³/h unit with 1200 Pa total pressure needs about 11.3 kW at the motor input with the efficiencies assumed below, a specific fan power of 2.03 kW per m³/s.
- Cutting 140 Pa by lowering face velocity at the filters and coil saves about 1.3 kW, or 11,501 kWh a year.
- Every 100 Pa removed saves about the same fraction of power, so the largest items in the budget are the best targets.
- DOE guidance warns that decisions based on lowest first cost rather than life-cycle cost can be unwise, and fan systems are the textbook case.[1]
The pressure budget
Fan total pressure is the sum of the resistances along the air path. The values below are illustrative for a modern unit with a heat recovery wheel. Your unit’s figures come from the component datasheets and the duct design.
| Component | Pressure drop (Pa) |
|---|---|
| Outdoor air louvre and damper | 60 |
| Prefilter (coarse) | 80 |
| Fine filter (ePM1 stage) | 180 |
| Cooling coil, wet | 160 |
| Heat recovery wheel (one pass) | 120 |
| Internal casing and transitions | 90 |
| Supply duct and terminals | 400 |
| Return path | 110 |
| Total | 1200 |
The duct and terminals take the largest share, and they belong to the system designer, not the unit supplier. Of the parts inside the unit, the fine filter, the coil and the wheel dominate, and those are all areas where face velocity is the design choice.
From pressure to power
Fan air power is airflow in m³/s times total pressure in Pa, divided by 1,000 for kW. Divide that by the efficiency of each stage: fan, motor and drive. We assume 65% fan efficiency, a 93% motor and a 98% drive, which are typical-style numbers and not those of any named product. The motor class matters: IEC 60034-30-1 defines IE3 and IE4 classes, and each step cuts motor losses by roughly 20%, with a 15 kW four-pole motor at 92.1% in IE3 and 93.9% in IE4.[2]
Worked example. Air power = 5.56 m³/s × 1200 Pa ÷ 1,000 = 6.67 kW. Electrical input = 6.67 ÷ (0.65 × 0.93 × 0.98) = 11.3 kW. Specific fan power (SFP) is that power divided by the airflow in m³/s: 11.3 ÷ 5.56 = 2.03 kW per m³/s. Running 8,760 hours at USD 0.10 per kWh that is 98,580 kWh and about USD 9,858 a year.
What a few design choices save
Take the same unit and make two changes: add a second row of filter modules so the fine filter’s velocity falls, and choose a coil with a larger face area. Suppose together they remove 80 Pa from the filter and 60 Pa from the coil. The pressure falls from 1200 to 1060 Pa, and the power from 11.3 to 9.9 kW.
| Design | Total pressure (Pa) | Fan input power (kW) | SFP (kW per m³/s) | Energy (kWh/year) | Cost at USD 0.10/kWh |
|---|---|---|---|---|---|
| Base | 1200 | 11.3 | 2.03 | 98,580 | USD 9,858 |
| Larger filter and coil face | 1060 | 9.9 | 1.79 | 87,079 | USD 8,708 |
The saving is 1.3 kW, about 12% of the fan power, from two changes whose extra cost is a bigger casing section. Over a ten-year life it dwarfs the price. The same logic applies to the filter bank on its own, covered in our guide to face area and pressure drop.
Part load and variable speed
Fan power falls with the cube of speed, so a unit that spends most of its hours below full airflow gains most from a variable speed drive. A fan at 80% speed uses about half the power. That makes the duty profile, not the design point, the number to use when estimating annual energy, and it favours specifying the fan efficiency at the part-load points too. Heat recovery adds its own pressure drop that must be weighed against the energy it recovers, as we show with numbers in energy recovery in hot, humid climates.
What to ask the supplier
- The fan total pressure at design, split by component, with the assumptions about filter condition (clean or dirty).
- The fan, motor and drive efficiencies, and the motor efficiency class.
- The specific fan power at design airflow, and the energy at part load if the unit has variable speed.
- The face velocity of the filter and coil, and whether a larger option is available.
- Whether the pressure drop figures are for clean or loaded filters. A fan chosen on clean-filter pressure will fall short as the filters load.
The ventilation rate itself, which sets the airflow, is a separate decision. The method for deriving airflow from the cooling load is in from cooling load to AHU airflow.
Where this fits with NextAir
NextAir’s AHUs are specified with the pressure budget and fan efficiency stated, so you can compare them on energy and not just on airflow. Send the airflow, external static pressure and filter classes to our air handling unit manufacturer team. Our guide to air handling units explains static pressure and fan sizing, and the healthcare page shows a continuous-duty case where energy matters most.
Sources
- Plant Engineering (US DOE Motor System BestPractices material). Building energy efficiency into fan systems.
- Fabrico (summary of IEC 60034-30-1). IE3 vs IE4 motors: efficiency classes explained (IEC 60034-30-1).
Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.
Frequently Asked Questions
What is specific fan power?
The electrical power a fan system uses divided by the airflow it moves, usually in kW per m³/s. It lets you compare fan efficiency between units of different sizes.
How do I calculate fan power for an AHU?
Multiply airflow in m³/s by total pressure in Pa, divide by 1,000, then divide by the product of fan, motor and drive efficiencies.
What is the biggest part of an AHU's pressure drop?
Usually the duct system outside the unit, followed by the fine filter, the cooling coil and any heat recovery device inside it.
Does a higher efficiency motor matter?
Yes. Each IEC 60034-30-1 class step cuts motor losses by roughly 20%, though the gain in efficiency points narrows as motor size grows.
Why choose a larger coil or filter bank?
Lower face velocity means lower pressure drop and lower fan energy for the life of the unit, which usually outweighs the extra cost of the bigger casing.