Water is the consumable of an evaporative system, and in the regions that buy most air washers it is also scarce and expensive. The consumption can be calculated from first principles in a few lines, and the result tells you both what the system costs to run and how hard to push the water treatment.

We work through the evaporation, the bleed-off that keeps the water from turning to brine, and the make-up total, for a 10,000 m³/h washer.

The short version

  • A 10,000 m³/h washer at 40 °C and 20% RH with 85% efficiency evaporates about 68 kg of water an hour, around 1,636 litres a day.
  • Bleed-off, the water drained to limit dissolved solids, is evaporation ÷ (cycles of concentration − 1). At 4 cycles it is a third of the evaporation.
  • Total make-up at 4 cycles is about 90.9 kg/h. At 2 cycles it is 136.3 kg/h.
  • Water management for Legionella is part of the same system, and ASHRAE Standard 188 sets a framework for it.[1][2]

Evaporation: set by the air

The water the air picks up is the dry air mass flow times the rise in humidity ratio across the washer. For 10,000 m³/h at 40 °C and 20% RH, the dry air flow is 3.09 kg/s. The air enters at 9.2 g/kg and, at 85% efficiency, leaves at 15.3 g/kg, a rise of 6.1 g/kg.

Worked example. Evaporation = 3.09 kg/s × 0.00613 × 3,600 = 68 kg/h, which is 68 litres an hour, or 1,636 litres a day. Check it against the cooling: 68 kg/h × 2,450 kJ/kg ÷ 3,600 is about 46 kW, which matches the sensible cooling the air gives up. The water use is not an extra assumption. It is the cooling expressed in litres.

Notice the dependence on the weather. The same washer in a more humid climate evaporates less, because there is less cooling potential, as shown in the wet-bulb depression article. The water use is highest on the hot, dry days when you most want the cooling.

Bleed-off: set by the water

Evaporation leaves the dissolved minerals behind, so the recirculating water gets saltier. To hold the concentration steady, some water is drained, which is the bleed-off or blowdown. The standard relationship comes from a salt balance: the make-up water carries minerals in, the bleed carries them out, and the evaporated water carries none.

  • Cycles of concentration (COC) = concentration in the sump ÷ concentration in the make-up water.
  • Bleed = evaporation ÷ (COC − 1).
  • Make-up = evaporation + bleed (+ a small drift loss, ignored here).
Cycles of concentrationEvaporation (kg/h)Bleed-off (kg/h)Make-up (kg/h)Make-up (litres/day)Bleed as share of make-up (%)
268.168.1136.33,27150.0
368.134.1102.22,45333.3
468.122.790.92,18125.0
568.117.085.22,04420.0
668.113.681.81,96316.7

Raising the cycles from 2 to 4 cuts the make-up from 136.3 to 90.9 kg/h, a saving of 45.4 kg/h. Going from 4 to 6 saves a further 9.1 kg/h. The returns diminish, because the evaporation is a floor that no amount of treatment removes.

Why you cannot just raise the cycles

More cycles mean saltier water, and saltier water scales the media, corrodes metal and feeds microbial growth if it is not controlled. The limit depends on the hardness and other minerals in the make-up, the materials in the washer and the treatment programme. The make-up quality is the first thing to analyse. Soft water allows high cycles. Hard water caps them unless it is softened first.

There is also a safety dimension. Systems that aerosolize recirculating water can spread Legionella if it is not managed, and ASHRAE Standard 188 asks owners of buildings with such non-potable water systems to have a water management plan.[1][2] We discuss it in Legionella risk in evaporative systems. Bleed-off is part of that plan, not just a cost.

What it costs

Annual water follows from the table. At 4 cycles the washer needs about 90.9 litres an hour, so over 3,000 hours of operation it uses about 273 m³. Here is the yearly cost at three illustrative water prices, which you should replace with your own tariff:

Water price (USD per m³)Annual cost at 4 cycles (USD)Annual cost at 2 cycles (USD)
1273409
38181,227
61,6362,453

In a region where water is expensive or must be desalinated, treatment that lets you run at 5 or 6 cycles instead of 2 can pay for itself quickly, and softening the make-up is often the first step. The treatment chemistry is the specialist’s job. The arithmetic of what it saves is above.

Where the water can come from

  • Mains or borehole water, softened if hard.
  • Treated wastewater or recycled water, where the application and local rules allow, with attention to what it contains.
  • Cooling coil condensate from air handling units, which is nearly mineral-free. A 10,000 m³/h coil can make hundreds of litres an hour in humid weather, as we calculate in the condensate article.

Measure the real consumption with a make-up meter from the first day. A meter is cheap, it turns a design number into a number you manage, and a sudden rise in make-up is often the first sign of a leak, a stuck float valve or a bleed set too high.

Where this fits with NextAir

NextAir’s air washers include the sump, make-up and bleed connections sized for your water quality, and we can include conductivity-controlled bleed. Send the airflow, the design weather and your make-up water analysis to our industrial air washer manufacturer team. Our air washer guide covers water treatment, and the textile and food manufacturing pages cover typical duties.

Sources

  1. Environmental Law Institute. Legionella Management in Building Water Systems: summary of ASHRAE Standard 188.
  2. ASHRAE. Standard 188-2021 fact sheet.

Figures and tables on this page are calculated or compiled by NextAir Systems and you are welcome to reuse them with a link back to this article.

Frequently Asked Questions

How much water does an air washer use?

For 10,000 m³/h at 40 °C and 20% RH with 85% efficiency, about 68 litres an hour is evaporated, plus bleed-off. At 4 cycles of concentration the total make-up is about 90.9 litres an hour.

What is bleed-off?

Water drained from the sump to stop dissolved minerals building up. It equals evaporation divided by the cycles of concentration minus one.

What are cycles of concentration?

The ratio of dissolved mineral concentration in the recirculating water to that in the make-up water.

Can I reduce water use?

Yes, by raising the cycles with better treatment or softened make-up, and by using condensate or recycled water. Evaporation itself cannot be avoided because it is the cooling.

Does the water use depend on the weather?

Yes. A washer evaporates most on hot, dry days, when the wet-bulb depression is largest.