Steam-Reactivated Desiccant Dehumidifier Manufacturer: Cutting Electrical Load on Large Units

NextAir Systems, Faridabad, India. Last reviewed October 2026.

On a large desiccant dehumidifier, the heater is the largest electrical load by far. If your site already makes steam or hot thermal fluid, using it to reactivate the rotor can take most of that load off the electrical supply, and cost less to run. If your site has neither, it is the wrong option, and electric reactivation stays the simple answer.

NextAir offers steam or thermal-fluid reactivation in place of electric on its ND series, and we recommend it above ND-7500 where site utilities support it. This page explains what it involves and how to check whether it pays.

At a glance

  • Steam or thermal-fluid reactivation is an option on our ND units, recommended above ND-7500 where the site utilities support it.
  • On one published datasheet, the electrical supply of a large rotor unit falls from 165 kW with an electric heater to 15 kW with steam, water or gas reactivation.[1]
  • Using that datasheet’s heat-to-capacity ratio (1.46 kWh per kg of water) as an illustration, an ND-15000 at its rating would need about 197 kW of heat, or roughly 337 kg/h of steam at an assumed latent heat of 2,107 kJ/kg.
  • The saving depends on what your heat costs. Free waste heat transforms the case, and expensive boiler fuel can erase it.

Why large units favour non-electric heat

Reactivation needs hot air, and heating air with electricity is the most expensive way to make heat in most countries. A small unit uses a modest heater and the convenience of electricity wins. A large unit uses tens or hundreds of kilowatts, which affects the transformer, the cabling and the monthly bill. That is why we recommend steam or thermal-fluid reactivation above ND-7500, where the utilities support it, and why it is the first question to ask on any large quotation.

The published datasheet of one rotor unit makes the point: its electrical supply is 165 kW with an electric heater and 15 kW when reactivation is by steam, water or gas, because the 15 kW is only the fans, the drive and the controls.[1] The same split, of course, applies in principle to any rotor dehumidifier, though the figures are specific to each machine.

How the heat is counted

The heat duty of reactivation scales with the moisture removed. On the datasheet quoted above, the heater accounts for about 150 kW against a capacity of 102.6 kg/h, which is 1.46 kWh per kg of water.[1] Applying that ratio to our ND models is an illustration only: our own heat duty is stated for your conditions on the quotation, and depends on rotor, reactivation temperature and heat recovery. The table shows what it would mean in steam, using a standard steam-table latent heat of about 2,107 kJ/kg at 5 bar absolute.

ModelMoisture removal at rating (kg/h)Illustrative heat duty (kW)Illustrative steam (kg/h)
ND-1000090.0132225
ND-12500112.5164281
ND-15000135.0197337
ND-20000180.0263450

The steam figures are for sizing the boiler capacity and pipework you would need to dedicate. If your boiler is already fully loaded, the extra steam may need new capacity, and the cost case changes. Ask your supplier for the heat duty at your condition and the steam pressure and condensate arrangement they assume.

What the heat costs

The comparison is between the cost of a kilowatt-hour of electric heat and the cost of a kilowatt-hour of steam heat, which is the fuel price divided by boiler efficiency. With a gas-fired boiler at an assumed 85% efficiency, the cost per kWh of heat is the gas price per kWh divided by 0.85. The table uses illustrative prices, and you should replace them with yours.

Electricity (per kWh)Gas (per kWh of fuel)Electric heat (per kWh)Steam heat at 85% (per kWh)
USD 0.06USD 0.03USD 0.060USD 0.035
USD 0.10USD 0.04USD 0.100USD 0.047
USD 0.15USD 0.06USD 0.150USD 0.071

Worked example. At illustrative prices of USD 0.10 per kWh for electricity and USD 0.04 for gas, a kilowatt-hour of heat costs USD 0.100 from the electric heater and about USD 0.047 from the boiler, a little under half. If the steam is waste heat from a process, the marginal cost may be close to zero. If the boiler runs on expensive fuel or is already at capacity, the saving shrinks. The full energy picture is in where the power goes in a desiccant dehumidifier.

Also consider the control side. A steam-reactivated unit needs a modulating valve and a trap set, and its reactivation temperature is held by steam pressure and flow, not by switching heater stages. Ask the supplier how the control works at part load and what the unit does when the steam supply drops, because a boiler trip should not leave a cold store without humidity control.

When to stay with electric

  • No steam or thermal fluid on site, or a distant boiler house that would need long, insulated piping.
  • Small units, where the extra pipework costs more than the electricity saves.
  • Intermittent running, where the boiler would sit idle between short runs.
  • A site where the electrical supply is not the constraint and the heat is cheap electricity.

What to send us

The steam pressure and temperature available, whether condensate return exists, the connected boiler capacity, and the model you are considering. For a very large duty we will compare a steam-reactivated bank with an electric one on your tariffs. Compare suppliers using how to choose a desiccant dehumidifier manufacturer, and see how our rotor dehumidifiers are built.

What to send us for a quotation

  • Model or airflow and the entering air condition
  • Steam pressure and temperature, or thermal-fluid temperature, available at the unit
  • Whether condensate return exists
  • Spare boiler capacity
  • Electricity and fuel prices
  • Voltage, frequency and the space for the unit and pipework

Send these to us through our contact page and we will give the heat duty at your conditions. See the desiccant dehumidifier range and our guidance for cold storage and food industry sites, where large units are common. Our dehumidifier guide covers the technology, and a boiler house often serves an air handling unit too.

Sources

  1. Destech (UAB Desiccant Technologies Group). Desiccant dehumidifier MDC 18000 technical datasheet.

Types and variants we build

Frequently Asked Questions

Do you offer steam-reactivated desiccant dehumidifiers?

Yes. Steam or thermal-fluid reactivation is an option on our ND series in place of electric, recommended above ND-7500 where site utilities support it.

Why use steam instead of electric heat?

Because on large units the heater dominates the electrical load, and steam heat usually costs less than electric heat. On one published datasheet the supply falls from 165 kW to 15 kW.

How much steam does a dehumidifier use?

It depends on the model, rotor and reactivation temperature. As an illustration only, about 2.5 kg of steam per kg of water removed, using a published unit's heat ratio and a latent heat of 2,107 kJ/kg.

When is electric reactivation better?

When there is no steam or thermal fluid on site, on small units, and when running is intermittent.

Will you state the heat duty on the quotation?

We state it for your conditions and the heat source, so you can size the boiler capacity and compare running costs.

Talk to Our Engineering Team

Call +91-9311805618 or use our contact form for a facility-specific recommendation.

Contact Us