A textile hall has a heat problem and a humidity problem, and in a hot, dry climate they have one solution. Machines make heat. Fibres want moist air. An air washer cools the air by evaporating water into it, which is exactly the swap a mill needs: cooler and more humid air in a single step.
NextAir builds industrial air washers up to 50,000 CFM per unit for textile departments, with multi-bank arrangements for larger halls. This page shows how to turn a hall’s heat load into an airflow and a unit count, and what to check about your climate first.
At a glance
- A 300 kW heat load, with supply air at about 26.1 °C from a washer at 42 °C and 20% RH, and the hall allowed to run 6 K above supply, needs about 155,588 m³/h, which is 91,576 CFM or 2 units of 50,000 CFM.
- Textile departments are a listed duty for our air washers: a 12,500 CFM unit suits a production hall or textile department.
- The washer only works if the air is dry enough. Where the design wet-bulb is high, the cooling is limited, and we say so.
- Added humidity is a feature in a mill, not a cost, as long as it stays within what the process wants.
Why an air washer suits a textile hall
An air washer cools, cleans and humidifies the air in one evaporative process, which makes it one of the most energy-efficient ways to condition large volumes of air in hot, dry, dusty conditions. A textile department is all three: it is hot from the machinery, it is dusty with fibre, and the process runs better in humid air. The water-contact zone uses rotating discs, saturated cellulose pads or atomizing nozzles, depending on the configuration, with droplet eliminators and a water reservoir that recirculates, so only the evaporated water needs replacing.
Single-stage units mainly cool and remove dust. Two-stage units give tighter control of humidity and air purity, for tighter tolerances; see two-stage air washers. The mill should choose on what the process tolerates, and on the climate.
From heat load to airflow
The airflow to carry away a hall’s heat is the load divided by air density, specific heat and the allowed temperature rise between supply and hall. We take a 300 kW load as an example, supply air at 26.1 °C (what an 85% efficient washer delivers from 42 °C and 20% RH), and four allowed rises. The last column is the number of 50,000 CFM units, the largest we build as a single unit.
| Allowed rise over supply (K) | Hall temperature (°C) | Airflow (m³/h) | Airflow (CFM) | Units of 50,000 CFM |
|---|---|---|---|---|
| 4 | 30.1 | 233,382 | 137,365 | 3 |
| 6 | 32.1 | 155,588 | 91,576 | 2 |
| 8 | 34.1 | 116,691 | 68,682 | 2 |
| 10 | 36.1 | 93,353 | 54,946 | 2 |
The pattern is the usual one: a tighter allowed temperature costs more air, in this case 2.5 times as much between a 10 K and a 4 K rise. A mill that can accept a hall at 32 to 34 °C needs far less air than one that wants 30 °C. Whether any of this works depends on the weather, which is why the first step is the check in wet-bulb depression, and what supply you can expect is in saturation efficiency.
Humidity: too little, and too much
A washer raises the humidity of the air it cools. In a mill that is what you want, up to a point. Too dry and fibre becomes brittle and static builds; too humid and the process suffers differently. The supply condition of an evaporative system is limited by the wet-bulb, so in humid weather the washer adds moisture and cools little, as quantified in how much moisture an air washer adds. Ask the manufacturer to state the supply dew point as well as the temperature, and to say what happens on the worst humid day.
Water
Water is the consumable, and availability, quality and hardness matter more than most buyers expect. The evaporation and bleed-off arithmetic is in air washer water consumption, and the management of a recirculating system in Legionella risk and ASHRAE 188. Fibre and dust in the air load the water, so ask the supplier about filtering and cleaning.
Consider the dust too. A textile hall is full of fibre, and fibre blocks filters and spray nozzles faster than ordinary dust. Ask the supplier how the air is pre-filtered before the washer, how the water is filtered and cleaned, and how often the contact medium needs to be cleaned or replaced in your conditions. These are maintenance costs that never appear on the first quotation but decide how the plant behaves in its third year.
Multi-bank layouts
Above 50,000 CFM we build multi-bank arrangements, with several units side by side serving one hall or several departments. A 150,000 CFM requirement is three units. Beyond that, systems are custom-engineered. Where you want one department to keep working while another is cleaned, separate banks per department are an advantage.
For the supplier checklist, see how to choose an industrial air washer manufacturer, and for our textile guidance, the textile industry page.
What to send us for a quotation
- Hall dimensions, ceiling height and the machine heat load
- Design dry-bulb and wet-bulb temperatures for the site, and the worst humid day
- Temperature and humidity the process needs
- Water availability, quality and hardness
- Dust and fibre loading in the air
- Layout of the hall and the space for units and ducts
Send these to us through our contact page and we will recommend a unit, a bank or a custom design, or tell you plainly if an air washer is the wrong tool for your climate. A hall plan and the machine list are the most useful attachments, because they let us check the heat load as well as the airflow. See the air washer range, our guide to industrial air washers and our pages for Saudi Arabia and Egypt. Where humidity must be tightly held, add dehumidification.
Types and variants we build
- Multi-Bank Air Washer Supplier: Several 50,000 CFM Units Serving One Hall
Multi-bank air washers above 50,000 CFM: how many units a hall needs, what redundancy adds, and the water a large evaporative plant evaporates every hour. - Stainless Steel Air Washer Manufacturer: SS 304 and SS 316 Units, and Why Water Chemistry Decides the Grade
Stainless steel air washers in SS 304 and SS 316, alone or with a two-stage design: how recirculating water concentrates salts, with a calculated table. - Textile Humidification Plant Manufacturer: Air Washers That Cool and Humidify a Mill Hall
Air washers for textile departments: how a hall heat load becomes airflow, the number of 50,000 CFM units it needs, and why the added humidity helps a mill.
Frequently Asked Questions
Do you build air washers for textile mills?
Yes. Textile departments are a listed duty for our air washers, up to 50,000 CFM per unit, with multi-bank arrangements for larger halls.
How do I size an air washer for a textile hall?
Divide the hall's heat load by air density, specific heat and the allowed temperature rise over the supply air, then count units of up to 50,000 CFM.
Is the added humidity a problem?
In a textile mill it is usually a benefit, within what the process wants. Ask for the supply dew point, and check the worst humid day.
What if my climate is humid?
Evaporative cooling depends on dry air. Where the design wet-bulb temperature is high, the cooling is limited, and we evaluate your conditions first and say plainly if another technology suits better.
How much water does it use?
Evaporation plus bleed-off. The calculation is in our air washer water consumption guide.