HEPA and UV-C Central Air Purification System Manufacturer: What Each Stage Does and What It Costs
NextAir Systems, Faridabad, India. Last reviewed October 2026.
Combining HEPA filtration and ultraviolet light in one air purification system sounds like a double guarantee. It is two different jobs. HEPA removes particles, including those that carry microorganisms. Ultraviolet inactivates microorganisms in the air that passes through it. Neither removes odour or gases. Understanding which stage does what stops you paying for one and expecting the other.
NextAir manufactures central air purification systems with a MERV 8 pre-filter, a MERV 13-14 fine filter and a UV-C chamber as standard, with HEPA, ISO 16890 rated filtration and a gas-phase module as options, from 500 to 20,000 CMH.
At a glance
- Standard stages are a MERV 8 pre-filter, a MERV 13-14 fine filter and a UV-C chamber with about 0.45 seconds of residence time. HEPA means 99.97% at 0.3 microns, offered as an upgrade to, or in addition to, the fine filter.
- HEPA brings a larger fine-filter section and a higher pressure drop. Each 100 Pa of extra resistance costs about 0.46 kW on a 10,000 CMH unit, or 4,056 kWh a year.
- A HEPA class is only as good as its seal. A small bypass limits overall efficiency, as shown in our guide to reading a HEPA datasheet.
- For odour and VOC control, an optional gas-phase module is available, and dedicated adsorbers carry a higher loading where gas control is the main duty.
Three stages, three different jobs
| Stage | What it removes or does | What it does not do |
|---|---|---|
| MERV 8 pre-filter | Coarse dust, protecting the later stages | Fine particles, microorganisms, gases |
| MERV 13-14 fine filter | Fine particles in the ePM1 range | Gases, and the smallest particles at high efficiency |
| HEPA (99.97% at 0.3 microns) | Very fine particles, including those carrying microorganisms | Gases and odour; microorganisms already in the air stream are captured only if on particles |
| UV-C chamber (about 0.45 s residence) | Inactivates airborne microorganisms by dose | Particles, odour, gases |
| Gas-phase module (optional) | Odour and VOC, with proprietary media | Particles; capacity is smaller than a dedicated adsorber’s |
The National Air Filtration Association gives a rough equivalence between rating systems: ePM1 corresponds to about MERV 13 to 16.[1] That places our MERV 13-14 fine filter in the ePM1 range, and HEPA above it. ISO 16890 rated filtration is available where a PM-fraction specification is needed, and the rating systems are explained in MERV, ISO 16890 and EN 1822.
What HEPA means on a datasheet
HEPA at 99.97% at 0.3 microns is the US-style definition. The European EN 1822 classes grade filters at the most penetrating particle size, with H13 at least 99.95% and H14 at least 99.995%.[2] The two are close but not identical, so ask which standard a quotation uses and for the test report. The leak arithmetic matters as much as the class: a bypass of 0.1% of the airflow can limit overall efficiency to about 99.9% whatever the media, which is why how to read a HEPA datasheet recommends an installed leak test.
UV-C: dose, not just lamps
Ultraviolet effect depends on dose, which is irradiance times exposure time. With about 0.45 seconds of residence, lamp output and count are specified to the target organism. Ask for the dose, the organism and the lamp life, and keep the lamps accessible. Our standard unit tracks lamp hours on the local panel. UV-C does nothing about particles or gases, and its effect on a microorganism that is shielded inside a particle is limited, which is why it sits after the filters.
The running cost of the extra stage
A HEPA filter adds pressure drop, and the fan has to overcome it, every hour the system runs. The table shows what 100 Pa costs in fan power at 60% combined efficiency and continuous running, for five of our models. It illustrates the scale; the pressure drop of your HEPA stage is stated on the quotation.
| Model | Airflow (CMH) | Fan power per 100 Pa (kW) | Energy per 100 Pa (kWh/year) |
|---|---|---|---|
| NAP-2000 | 2,000 | 0.09 | 811 |
| NAP-5000 | 5,000 | 0.23 | 2,028 |
| NAP-10000 | 10,000 | 0.46 | 4,056 |
| NAP-15000 | 15,000 | 0.69 | 6,083 |
| NAP-20000 | 20,000 | 0.93 | 8,111 |
If a HEPA stage adds 250 Pa to a 10,000 CMH unit, that is about 10,140 kWh a year. The filter face area decides how much of that you pay, and the relationship is in filter face area, velocity and energy.
A practical consequence of the table above: if a quotation offers HEPA and UV-C together and a very low price, ask which stages are actually included, what the clean and final pressure drops are, and whether the lamps and the HEPA filter are covered by the stated warranty. The stages are easy to list and hard to compare without that detail, and the cheapest quotation is often the one with the thinnest filter section or the least accessible lamp bank.
Where HEPA and UV-C are specified
Healthcare, pharmaceutical and other critical areas, and any space where biological risk matters. HEPA is available for cleanroom, healthcare or biological-containment duties. See our healthcare and pharmaceutical pages. Access panels at every stage allow filter change-out and lamp service, a local panel shows the pressure differential across each filter stage, and stainless steel housing is an option for coastal or corrosive sites.
To compare suppliers, see how to choose an air purification system manufacturer.
What to send us for a quotation
- The duty: hospital, laboratory, pharmaceutical, commercial or other
- Airflow, or the room volume and the air change rate required
- The filtration standard required: MERV, ISO 16890 class or HEPA, and any leak-test requirement
- The organism or risk the UV-C must address
- Whether gas-phase control is needed
- Electrical supply, space and whether the site is coastal
Send these to us through our contact page and we will propose the stages and state the pressure drop. See the NAP range and our guide to centralized air purification. Where gases are the main concern, consider our dry VOC adsorbers, and the unit often serves an air handling system.
Sources
- National Air Filtration Association (NAFA). ISO 16890 user guide: understanding ePM and ISO Coarse.
- Camfil. Comparison chart: ASHRAE 52.2, ISO 16890, EN 779, EN 1822.
Types and variants we build
- Cleanroom Air Filtration System Supplier: From Air Changes to Airflow to Unit Size
Cleanroom air filtration: turn room volume and air change rate into airflow and a unit size, and see where our HEPA-capable NAP units fit in a project. - HEPA and UV-C Central Air Purification System Manufacturer: What Each Stage Does and What It Costs
HEPA and UV-C central air purification systems from 500 to 20,000 CMH: what particle, germicidal and gas stages each handle, and what 100 Pa of filter costs. - Modular Filter Module Air Purification Supplier: Why the 610 x 610 mm Grid Makes Maintenance Easier
Why central air purification units built on the standard 610 x 610 mm filter module are easier to size, stock and service, with a spares count for every model.
Frequently Asked Questions
Do you make air purification systems with HEPA and UV-C?
Yes. Our systems use a MERV 8 pre-filter, MERV 13-14 fine filter and UV-C chamber as standard, with HEPA at 99.97% at 0.3 microns as an upgrade to, or in addition to, the fine filter.
What does UV-C do in an air purifier?
It inactivates airborne microorganisms by dose. It does not remove particles, odour or gases.
Does HEPA remove odours?
No. HEPA removes particles. Odour and VOC control needs a gas-phase stage, which is optional in our units.
What is the airflow range?
500 to 20,000 CMH in a single unit, from NAP-0500 to NAP-20000, with banks or a sectionalised casing above that.
Does HEPA increase running cost?
Yes, through higher pressure drop. About 0.46 kW per 100 Pa on a 10,000 CMH unit at 60% efficiency, as an illustration.